– 194 –
Points to Note When Servicing Compressor
(1) When checking the outputs of inverters, remove the wiring from all the compressors.
How to Check Inverter Output
(1) Turn off the power supply.
(2) Remove compressor leads from the IPDU P.C. board (A3-IPDU). (Be sure to remove all the leads.)
(3) Turn on the power supply and start cooling or heating operation.
Be careful not to make simultaneous contact with two or more faston connectors for compressor leads or a
faston connector and some other object (e.g. the unit cabinet).
(4) Check the output voltage across each pair of inverter-side (CN703, 704, 705).
If the result is unsatisfactory according to the judgment criteria given in the table below, replace the IPDU
P.C. board.
* When connecting the compressor leads back to the compressor terminals after checking the output, check
the faston connectors thoroughly to ensure that they are not crooked. If there is any loose connector, tighten
it with a pair of pliers, etc. before connecting the lead.
How to Check Resistance of Compressor Winding
(1) Turn off the power supply.
(2) Remove compressor leads from the compressors.
(3) With each compressor, check the phase-to-phase winding resistances and winding-to-outdoor cabinet
resistance using a multimeter.
• Earth fault?
→
It is normal if the winding-to-outdoor cabinet resistance is 20M
Ω
or more.
• Inter-winding short circuit?
→
It is normal if the phase-to-phase resistances are in the 0.6-1.0
Ω
range. (Use a digital multimeter.)
How to Check Outdoor Fan Motor
(1) Turn off the power supply.
(2) Remove fan motor leads from the IPDU P.C. board for the outdoor fan (CN703-CN705).
(3) Rotate the fan by hand. If the fan does not turn, the fan motor is faulty (locked up). Replace the fan motor.
If the fan turns, measure the phase-to-phase winding resistances using a multimeter. It is normal if the
measurements are in the 1.14-1.70
Ω
range. (Use a digital multimeter.)
No.
Measured leads
Criterion
1
Red-White
380~580V
2
White-Black
380~580V
3
Black-Red
380~580V
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for MMY-MAP0804FT7(Z)
Page 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...