– 187 –
Check code
Location
of
detection
System status
Description
Error detection
condition(s)
Check items (locations)
Outdoor 7-segment display
Main
remote
controller
Check
code
Sub-code
L02
—
L02
Indoor unit
Stop of
corresponding
unit
In case of different outdoor
unit (Not corresponded to Air to
Air Heat Exchanger type)
• Check outdoor unit model.
(Check whether the outdoor
unit corresponds to Air to Air
Heat Exchanger type or not.)
Outdoor units
model
disagreement
error
—
—
L03
Indoor unit
Stop of
corresponding
unit
There is more than one header
unit in group.
• Check indoor addresses.
• Check for any change made
to remote controller
connection (group/individual)
since indoor address setting.
Duplicated
indoor header
unit
L04
—
L04
I/F
All stop
There is duplication in line
address setting for outdoor
units belonging to different
refrigerant piping systems.
• Check line addresses.
Duplicated
outdoor line
address
—
—
L05
I/F
All stop
More than one indoor unit has
been set up as priority indoor
unit.
• Check display on priority
indoor unit.
Duplicated priority
indoor unit
(as displayed on
priority indoor unit)
—
—
L07
Indoor
unit
Stop of
corresponding
unit
There is at least one stand-
alone indoor unit to which group
control cable is connected.
• Check indoor addresses.
Connection of
group control
cable to stand-
alone indoor unit
L08
—
L08
Indoor
unit
Stop of
corresponding
unit
Address setting has not been
performed for indoor units.
• Check indoor addresses.
Note:
This code is displayed when
power is turned on for the
first time after installation.
Indoor group /
addresses not
set
L10
—
L10
I/F
All stop
Jumper wire provided on P.C.
board for servicing I/F P.C.
board has not been removed as
required for given model.
Check model setting of P.C.
board for servicing outdoor I/F
P.C. board.
Outdoor capacity
not set
—
—
L20
Indoor unit
All stop
There is duplication in central
control address setting.
• Check central control
addresses.
Duplicated
central control
address
L28
—
L28
L29
L29
I/F
All stop
There are more than 3
outdoor units.
• Check No. of outdoor units
connected (Only up to 3 units
per system allowed).
• Check communication lines
between outdoor units.
• Check for defect in outdoor
P.C. board (I/F).
Too many
outdoor units
connected
L30
L30
Indoor unit
Detected indoor
address
Stop of
corresponding
unit
• Signal is present at external
error input terminal (CN80) for
1 minute.
When external device is
connected to CN80
connector:
1) Check for defect in external
device.
2) Check for defect in indoor
P.C. board.
When external device is not
connected to CN80
connector:
1) Check for defect in indoor
P.C. board.
External interlock
of indoor unit
I/F
All stop
Insufficient number of IPDUs
are detected when power is
turned on.
• Check model setting of
P.C. board for servicing
outdoor I/F P.C. board.
• Check connection of UART
communication connector.
• Check A3-IPDU, fan IPDU,
and I/F P.C. board for defect.
Error in No. of
IPDUs
—
—
L09
Indoor unit
Stop of
corresponding
unit
Capacity setting has not been
performed for indoor unit.
Set indoor capacity. (DN = 11)
Indoor capacity
not set
L06
L06
I/F
No. of priority
indoor units
All stop
More than one indoor unit
have been set up as priority
indoor unit.
• Check displays on priority
indoor unit and outdoor unit.
Duplicated priority
indoor unit
(as displayed on
indoor unit other
than priority
indoor unit)
Symbol O
signifies site of
IPDU error.
1
O
O
O
O
O
O
O
O
2
O
O
O
O
O
O
O
O
3
O
O
O
O
O
O
O
O
A3-IPDU Fan
IPDU
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
O
O
O
O
O
O
O
O
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for MMY-MAP0804FT7(Z)
Page 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...