Check code
Location
of
detection
System status
Description
Error detection
condition(s)
Check items (locations)
Outdoor 7-segment display
Main
remote
controller
Check
code
Sub-code
I/F
Detected
outdoor unit No.
Display of center
unit only
H07
H07
All stop
Operating compressor detects
continuous state of low oil level
for about 2 hours.
<All outdoor units in
corresponding line to be
checked>
• Check balance pipe service
valve to confirm full opening.
• Check connection and
installation of TK1, TK2, TK3,
TK4, and TK5 sensors.
• Check resistance
characteristics of TK1, TK2,
TK3, TK4, and TK5 sensors.
• Check for gas or oil leak in
same line.
• Check for refrigerant
entrapment inside compressor
casing and check for liquid
back.
• Check SV3A, SV3B, SV3C,
SV3D, SV3E, and SV3F
valves for defect.
• Check oil return circuit of oil
separator for clogging.
• Check oil equalizing circuit for
clogging.
• Check SV6 circuit leakage.
Low oil level
protection
I/F
01: TK1 sensor
error
02: TK2 sensor
error
03: TK3 sensor
error
04: TK4 sensor
error
05: TK5 sensor
error
H08
H08
H15
—
H15
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TK1
sensor connector.
• Check resistance
characteristics of TK1 sensor.
• Check for defect in outdoor
P.C. board (I/F).
Error in
temperature
sensor for oil level
detection
I/F
All stop
Discharge temperature of (TD2)
does not increase despite
compressor 2 being in
operation.
• Check installation of TD2,
TK1, TK2, TK3 sensor.
• Check connection of TD2,
TK4, TK5 sensor connector
and wiring.
• Check resistance
characteristics of TD2 sensor.
• Check for defect in outdoor
P.C. board (I/F).
TD2 sensor
miswiring
(incomplete
insertion)
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TK2
sensor connector.
• Check resistance
characteristics of TK2 sensor.
• Check for defect in outdoor
P.C. board (I/F).
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TK3
sensor connector.
• Check resistance
characteristics of TK3 sensor.
• Check for defect in outdoor
P.C. board (I/F).
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TK4
sensor connector.
• Check resistance
characteristics of TK4 sensor.
• Check for defect in outdoor
P.C. board (I/F).
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TK5
sensor connector.
• Check resistance
characteristics of TK5 sensor.
• Check for defect in outdoor
P.C. board (I/F).
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for MMY-MAP0804FT7(Z)
Page 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...