– 18 –
Selection of Pipe Size
Coupling size of brazed pipe
(Unit: mm)
Connected section
External size
Internal size
Standard outer dia.
of connected
copper pipe
Connected section
Min. thickness
of coupling
External size
Internal size
Min. depth of
insertion
Oval value
Standard outer dia.
(Allowable difference)
C
F
K
G
6.35
6.35 (±0.03)
6.45 (
)
7
6
0.06 or less
0.50
9.52
9.52 (±0.03)
9.62 (
)
8
7
0.08 or less
0.60
12.70
12.70 (±0.03)
12.81 (
)
9
8
0.10 or less
0.70
15.88
15.88 (±0.03)
16.00 (
)
9
8
0.13 or less
0.80
19.05
19.05 (±0.03)
19.19 (
)
11
10
0.15 or less
0.80
22.22
22.22 (±0.03)
22.36 (
)
11
10
0.16 or less
0.82
28.58
28.58 (±0.04)
28.75 (
)
13
12
0.20 or less
1.00
34.92
34.90 (±0.04)
35.11 (
)
14
13
0.25 or less
1.20
38.10
38.10 (±0.05)
38.31 (
)
15
14
0.27 or less
1.26
41.28
41.28 (±0.05)
41.50 (
)
15
14
0.28 or less
1.35
Screw size
M6
Power supply terminal
2.3 to 2.7
Tightening torque
(N•m)
K
ØC
G
ØF
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.03
-0.03
+0.03
-0.03
+0.06
-0.02
+0.04
-0.04
+0.08
-0.02
+0.08
-0.02
M8
Earth screw
5.5 to 6.6
M3.5
Communication wire terminal
1.2 to 1.4
Screw size and tightening torque
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for MMY-MAP0804FT7(Z)
Page 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...