– 132 –
Manual address setup from the remote controller
With indoor wiring work completed and outdoor wiring work not done—in cases where indoor unit addresses are
decided in advance from the wired remote controller, or in cases where addresses are change after address setup.
1
Arrange one indoor unit and one remote
controller set to 1 by 1.
2
Turn on the power.
3
Push the
SET
+
CL
+
TEST
buttons simultaneously for
4 seconds or more.
LCD begins blinking.
(Refrigerant line address)
4
Using the
TEMP
buttons, set the DN code to 12.
5
Using the
TIME
buttons, set up the line address
(match it with the line address on the interface
PC board of the header unit on the same
refrigerant line).
6
Push the
SET
button (OK when the display goes
on).
(Indoor address)
7
Using the
TEMP
buttons, set the DN code to 13.
8
Using the
TIME
buttons, set up the indoor
address.
(0001~0048)
9
Push the
SET
button (OK when the display goes on).
(Group address)
10
Using the
TEMP
buttons, set the DN code to 14.
11
Using the
TIME
buttons, set Individual = 0000,
Header unit = 0001, Follower unit = 0002.
12
Push the
SET
button (OK when the display goes on).
(Central control address)
13
Using the
TEMP
buttons, set DN code to 03.
14
Using the
TIME
buttons, set up the central
control address. (0001~0064)
15
Push
SET
button. (OK when display goes on).
16
Push the
TEST
button.
Setup is finished (“Setting up” blinks; when “Setting up”
goes off, operation is possible).
17
Return to the original wiring over remote
controllers.
Group address
Individual: 0000
Header unit: 0001
Follower unit: 0002
(Wiring example for 2 refrigerant lines)
Line 1
Line 2
Line 1
Line 2
Outdoor
Indoor 1
Indoor 2
Indoor 1
(Remote controller group control)
Indoor 2
Indoor 3
Indoor 1
Indoor 2
Indoor 1
Indoor 2
Indoor 3
Line address
Indoor address
1
1
1
Header
1
2
2
Follower Follower
Follower Follower
1
3
2
2
1
2
2
2
2
Outdoor
Outdoor
Outdoor
(Wiring during manual address setup)
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Group
address
In the above example, where remote controllers are not
yet wired, set the address manually after individually
connecting the wired remote controller.
After address setup, return to the original
wiring over remote controllers.
In cases of
remote controller
group control
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
DN code
(CODE No.)
Set
data
5, 8, 11, 14
6, 9, 12, 15
16
4
7
10
13
3
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for MMY-MAP0804FT7(Z)
Page 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...