– 8 –
Installation space
Provide the space required for installing and servicing the indoor unit.
Provide a clearance of at least 5 mm between the top panel of the indoor unit and ceiling.
Installation space
Ceiling height
It is hard for the warm air to reach the floor level if the ceiling height exceeds the standard dimension (set at the
time of shipment) in the table below. Therefore, the high-ceiling setting must be selected.
For details on how to select this setting, refer to the section “Installing indoor unit on high ceiling” in Applicable
controls of this manual.
Height list of ceiling possible to be installed
(Unit: m)
REQUIREMENT
• A high-ceiling installation can only be used for models UP007 to UP012 when the ratio of total connection capacity
of the indoor unit to the outdoor unit capacity is 100% or less. Do not use this kind of installation if this capacity is over
100%.
• It is possible to change how long the filter sign (signaling that it is time to clean the filter) is to stay lighted on the
remote controller in accordance with the installation conditions.
• It is also possible to raise the detection temperature for the heating if it is hard for the air conditioner to heat up the
environment satisfactorily due to a factor such as the location where the indoor unit is installed or the structure of the
room.
• For details on the setting, refer to the section “Installing indoor unit on high ceiling” and “To secure better effect of
heating” in Applicable controls of this manual.
Model: MMU-
Height: A
UP007 to UP015
300 mm or more
UP018 to UP056
350 mm or more
Model: MMU-
UP007 to UP030
UP036 to UP056
Set data
Standard (At shipment)
2.7
2.7
0000
High ceiling (1)
3.2
3.0
0001
High ceiling (3)
3.8
3.5
0003
1000 mm or more
Obstacle
10
00 mm o
r
mo
re
5 mm or
mo
re
1000 mm or more
Installation of wireless remote controller (Sold separately)
The signal receiving unit of indoor unit can receive a signal by distance within approx. 7 m. Based upon it,
determine a place where the remote controller is operated and the installation place.
• Operate the remote controller, confirm that the indoor unit receives a signal surely, and then install it.
• Keep 1 m or more from the devices such as television.
(Disturbance of image or noise may generate.)
• To prevent a malfunction and reception failure of the remote controller, select a place where it is not influenced
by a fluorescent light, equipment (Electronic whiteboard etc.) emitting infrared rays, or direct sunlight.
• Switching the setting (A-B selection) of the wireless remote controllers and the signal receiving unit enables two
indoor units installed in a room to be respectively operated using two wireless remote controllers.
Within 7 m
15-EN
16-EN