24
Check method
On the remote controller (Main remote controller, Central control remote controller) and the interface P.C. board of
the outdoor unit, a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C.
board) operation is provided. Therefore the operation status can be known. Using this self-diagnosis function, a fault
and the location of this fault within the air conditioning system can be located, as shown in the table below.
Check code list
The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of a fault from the indoor remote controller: See “Main remote controller display” in the list.
• In case of a fault from the outdoor unit: See “Outdoor 7-segment display” in the list.
• In case of a fault from the indoor unit with a wireless remote controller:
See “Sensor block display of receiving unit” in the list.
Terminology
AI-NET : Artificial Intelligence.
IPDU : Intelligent Power Drive Unit
¡
: Lighting,
¤
: Flashing,
l
: Goes off
ALT. : Flashing is alternately when there are two flashing LED.
SIM : Simultaneous flashing when there are two flashing LED.
Check code
Wireless remote controller
Outdoor 7-segment display
Sensor block display
of receiving unit
Main
remote
controller
display
Auxiliary code
AI-NET central
control display
Operation
Timer Ready Flash
Check code name
Judging device
E01
—
—
—
¤
l l
Communication error between indoor and remote
controller (Detected at remote controller side)
Remote controller
E02
—
—
—
¤
l l
Remote controller transmission error
Remote controller
E03
—
—
97
¤
l l
Communication error between indoor and remote
controller (Detected at indoor side)
Indoor
E04
—
—
04
l
l
¤
Communication circuit error between indoor/outdoor
(Detected at indoor side)
Indoor
E06
E06
No. of indoor units in which
sensor has been normally
received
04
l
l
¤
Decrease of No. of indoor units
I/F
—
E07
—
—
l
l
¤
Communication circuit error between indoor/outdoor
(Detected at outdoor side)
I/F
E08
E08 Duplicated indoor addresses
96
¤
l l
Duplicated indoor addresses
Indoor / I/F
E09
—
—
99
¤
l l
Duplicated main remote controllers
Remote controller
E10
—
—
CF
¤
l l
Communication error between indoor MCU
Indoor
E12
E12
01: Indoor/Outdoor
communication
02: Communication between
outdoor units
42
¤
l l
Automatic address start error
I/F
E15
E15
—
42
l
l
¤
Indoor is nothing during automatic addressing
I/F
E16
E16
00: Capacity over
01 ~: No. of connected units
89
l
l
¤
Capacity over / No. of connected indoor units
I/F
E18
—
—
97, 99
¤
l l
Communication error between indoor units
Indoor
E19
E19
00: Header is nothing
02: Two or more header units
96
l
l
¤
Outdoor header units quantity error
I/F
E20
E20
01: Outdoor of other line
connected
02: Indoor of other line
connected
42
l
l
¤
Other line connected during automatic address
I/F
E23
E23
—
15
l
l
¤
Sending error in communication between outdoor units
I/F
E25
E25
—
15
l
l
¤
Duplicated follower outdoor addresses
I/F
E26
E26
No. of outdoor units which
received signal normally
15
l
l
¤
Decrease of No. of connected outdoor units
I/F
E28
E28 Detected outdoor unit number
d2
l
l
¤
Follower outdoor unit error
I/F
E31
E31
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 error
04: Fan IPDU error
05: IPDU + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error
CF
l
l
¤
IPDU communication error
I/F