SMMS High-Wall Type
Installation Manual
– 21 –
10.
Electric Work
WARNING
•
Use the specified wires for wiring connect the terminals. Securely fix them to prevent external
forces applied to the terminals from affecting the terminals.
Incomplete connection or fixation may cause a fire or other trouble.
•
Connect earth wire. (grounding work)
Incomplete grounding cause an electric shock.
Do not connect earth wires to gas pipes, water pipes, lightning conductor or telephone earth wires.
•
Appliance shall be installed in accordance with national wiring regulations.
Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire.
CAUTION
• If incorrect / incomplete wiring is carried out, it will cause an electrical fire or smoke.
• Install an earth leakage breaker that is not tripped by shock waves.
If an earth leakage breaker is not installed, an electric shock may be caused.
• Use the cord clamps attached to the product.
• Do not damage or scratch the conductive core and inner insulator of power and inter-connecting wires
during peeling them.
• Use the power cord and Inter-connecting wire of specified thickness, type, and protective devices
required.
•
Do not connect 220 V – 240 V power to the terminal blocks
(
,
,
A
,
B
)
for control wiring.
(Otherwise, the system will fail.)
• Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe.
The coating may melt resulting in an accident.
REQUIREMENT
• For power supply wiring, strictly conform to the Local Regulation in each country.
• For wiring of power supply of the outdoor units, follow the Installation Manual of each outdoor unit.
• Perform the electric wiring so that it does not come to contact with the high-temperature part of the
pipe.The coating may melt resulting in an accident.
• After connecting wires to the terminal blocks, provide a trap and fix wires with the cord clamp.
• Run the refrigerant piping line and control wiring line in the same line.
• Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.
21-EN