![Toshiba MMF-UP0151H-E Installation Manual Download Page 21](http://html.mh-extra.com/html/toshiba/mmf-up0151h-e/mmf-up0151h-e_installation-manual_423827021.webp)
– 20 –
Wireless remote controller
1
Turn on the power of the air conditioner.
When power is turned on for the first time
after installation, it takes approx. 5 minutes
until the remote controller becomes
available. In the case of subsequent power-
on, it takes approx. 1 minute until the remote
controller becomes available. Execute a test
run after the predetermined time has
passed.
2
Push “ON/OFF” button on the remote
controller, select [ Cool] or [
Heat] with
“MODE” button, and then select
[
HIGH] with “FAN” button.
3
4
5
6
Repeat procedures
4
→
5
→
4
→
5
.
Indicators “Operation” (green), “Timer”
(green), and “Ready” (orange) in the
wireless receiver section flash in approx. 10
seconds, and the air conditioner starts
operation. If any of these indicators does not
flash, repeat procedures 2 to 5.
7
Upon completion of the test run, push
“ON/OFF” button to stop operation.
<Overview of test run operations using the wireless
remote controller>
▼
Cooling test run:
ON/OFF
→
17°C
→
18°C
→
17°C
→
18°C
→
17°C
→
18°C
→
17°C
→
(test run)
→
ON/OFF
▼
Heating test run:
ON/OFF
→
30°C
→
29°C
→
30°C
→
29°C
→
30°C
→
29°C
→
30°C
→
(test run)
→
ON/OFF
Cooling test run
Heating test run
Set the temperature to 17°C
with the temp. setup buttons.
Set the temperature to 30°C
with the temp. setup buttons.
Cooling test run
Heating test run
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 18°C with the
temp. setup buttons.
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 29°C with the
temp. setup buttons.
Cooling test run
Heating test run
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 17°C with the
temp. setup buttons.
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 30°C with the
temp. setup buttons.
10
Maintenance
<Daily maintenance>
▼
Cleaning of air filter
Be sure to stop the air conditioner before cleaning of air
filter, then turn off the circuit breaker.
1
Push the ON/OFF button to stop the
operation, then turn off the circuit breaker.
2
Use a screwdriver to unfasten the screws of
the intake grille (two places) to open the
intake grille. The screws are designed to
stay on the intake grille.
3
Take out the air filter.
• Pull up the air filter toward you.
• Cleaning with water or vacuum cleaner
• If dirt is heavy, clean the air filter by tepid
water with neutral detergent or water.
• After cleaning with water, dry the air filter
sufficiently in a shade place.
• To attach the air filter, insert it into the unit and
push it in.
4
Close the intake grille and fasten the screws
(two places).
5
Turn on the circuit breaker, then push the
ON/OFF button on the remote controller to
start the operation.
▼
To open the access panel
Use a screwdriver to unfasten the screws of the access
panel (two places), slide the cabinet upward by
approximately 30 mm, and pull it out toward you.
CAUTION
Do not start the air conditioner while leaving air filter
removed.
Screw
Screw
Access panel
39-EN
40-EN
Summary of Contents for MMF-UP0151H-E