background image

2

MMD-AP___1HF2UL

E15-3S2

1. System summary

Outside Air Unit Type

• Connectable outdoor unit

Outdoor unit of SMMS-e series.

• Corresponding system

Corresponds to a system in which there are the outside air units and the indoor air
conditioners.

• Definition

The outside air unit means an air controller for taken-in outside air.
Intake of the outside air often influences on the system so that the normal control of the air conditioner
becomes difficult or gives a large load upon air controller and cooling performance.
Therefore it is frequently adopted to handle the outside air to a certain condition before the outside air
will enter in the main air conditioner.
This handling device is called an outside air unit.

NOTE:

The outside air unit is an air conditioner provided to handle the outside air load and is not to control
the room temperature. For correspondence to the load of the indoor air controller, set an air
conditioner separately.

Summary of Contents for MMD-AP0481HF2UL

Page 1: ...pe Contents 1 System summary 2 Specifications 3 Dimensions 4 Center of gravity 5 Piping diagram 6 System combination 7 Wiring diagram 8 Electrical characteristics 9 Fan characteristics 10 Sound data MMD AP0481HF2UL MMD AP0721HF2UL MMD AP0961HF2UL ...

Page 2: ...the system so that the normal control of the air conditioner becomes difficult or gives a large load upon air controller and cooling performance Therefore it is frequently adopted to handle the outside air to a certain condition before the outside air will enter in the main air conditioner This handling device is called an outside air unit NOTE The outside air unit is an air conditioner provided t...

Page 3: ...6 0 74 1 00 0 41 0 85 External static pressure factory default 208 V H M L In WG 0 75 0 55 0 16 0 84 0 74 0 24 0 67 0 41 H L 230 V H M L In WG 1 06 0 86 0 50 1 08 1 00 0 65 1 01 0 85 H L Air flow limit Lower limit cfm 445 693 866 Upper limit cfm 700 1088 1360 Air filter Field supply Controller Wired remote controller Connecting pipe Gas pipe In 5 8 7 8 Liquid pipe In 3 8 1 2 Drain pipe In VP25 Pol...

Page 4: ...er 7 9 200 Service space 7 9 200 Over 39 4 1000 Outside Air Unit Outside Air Unit Flexible duct Filter Box Filter Flexible duct Ceiling Air intake duct Access Area Outside air Over 3 9 100 Over 2 0 50 Air flow 23 0 583 Outside 15 1 383 Outside Suction Discharge temp sensor Discharge 28 7 728 Outside 13 7 347 Outside 0 7 18 2 3 59 2 5 65 2 6 65 0 4 9 2 6 5 12 8 65 5 325 Screw hole for duct mounting...

Page 5: ...e Access Area 23 6 600 Service space Over 7 9 200 Service space 7 9 200 Over 39 4 1000 Outside Air Unit Outside Air Unit Flexible duct Filter Box Filter Flexible duct Ceiling Air intake duct Access Area Outside air Over 3 9 100 Over 2 0 50 4 0 100 6 6 166 1 3 33 Ø1 26 Hole for control wire Ø7 8 22 2 Hole for power supply cable and remote control wiring Z view Installation Notice 1 Provide access a...

Page 6: ...6 MMD AP___1HF2UL E15 3S2 4 Center of gravity Z Y X Electrical box Model name MMD AP0481HF2UL AP0721HF2UL AP0961HF2UL X In Weight lb 26 4 18 9 8 7 212 26 4 30 3 8 7 349 Z In Y In ...

Page 7: ...or CN104 2P White 1 Detects indoor suction temperature 2 TC1 Connector CN100 3P Brown 1 Controls PMV super heat in cooling operation 3 TC2 Connector CN101 2P Blue 1 Controls PMV sub cool in heating operation 4 TCJ Connector CN102 2P Yellow 1 Controls PMV super heat in cooling operation 5 TF Connector CN103 2P Green 1 Detects indoor discharge temperature M Liquid side Gas side Strainer Pulse Motor ...

Page 8: ...decided for each capacity type 2 Combination of Indoor units is decided for Outdoor unit capacity type It allows only the combinations of Indoor units below Please refer to Outside Air Unit s Installation Manual except the above contents L U 2 F H 1 6 9 0 P A L U 2 F H 1 2 7 0 P A L U 2 F H 1 8 4 0 P A D M M e m a n l e d o m t i n u r o o d n I 6 9 0 2 7 0 8 4 0 e p y t y t i c a p a c t i n u r ...

Page 9: ...1 2 9 4 L1 c Actual length 0 3 1 7 2 4 Main piping length Equivalent length Max 394 0LQ Max 120 Min L1 Actual length Max 328 Min 164 Max 100 Min 50 Farthest equivalent piping length from the first branching section Li 1 Equivalent length c 0 3 8 9 Farthest equivalent piping length between Outdoor units LO Equivalent length Maximum equivalent piping length of Outdoor unit connecting pipe Equivalent...

Page 10: ...eight between indoor units H2 Case of All Outside Air connection to Side Blow SMMS e The combination which can connect Outside Air Unit is only the 1 1 combination of MCY MAP0487HS UL and MMD AP0481HF2UL Other combination is not permitted Correct Incorrect Allowable length height difference of refrigerant piping Case of All Outside Air CAUTION Length and height of refrigerant piping keep the limit...

Page 11: ...port connecting flange MMD AP072 type AP096 type Air supply port connecting flange Air intake port connecting flange Air intake port connecting flange 42 6 1083 25 6 650 2 6 10 65 16 2 6 65 1 8 45 0 7 19 0 4 9 2 6 65 13 7 347 0 4 9 12 8 325 2 6 5 65 5 0 4 9 0 7 19 42 6 1083 40 9 1040 2 6 16 65 16 2 6 65 1 8 45 0 7 19 0 4 9 2 6 65 13 7 347 0 4 9 12 8 325 2 6 5 65 5 0 4 9 0 7 19 23 0 583 20 5 520 2 ...

Page 12: ...an be drained even if rainwater enters in Wrap the outside of the intake duct with heat insulator because it intakes cold air while heating 2 Air supply duct Connect the air supply duct Locally procured to the Air supply flange Wrap aluminum tape around connecting part of the air supply port flange and duct or apply packing so that air does not leak Wall 1 Locally procured Access Area 23 6 23 6 in...

Page 13: ...s to be damaged and other such problems to result Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to deteriorate or the unit to shut down Locations where an in house power generator is used for the power supply The power line frequency and voltage...

Page 14: ...0 C humidity 80 or higher 1 Installation to inside of the ceiling with tiles on the roof 2 Installation to inside of the ceiling with slated roof 3 Installation to inside of the ceiling with kitchen In the above cases additionally attach the heat insulator Glass wool etc to all positions of the air conditioner which come to contact with the high humidity atmosphere In this case arrange the side pl...

Page 15: ...ich you purchased the air conditioner 1 When 096type system with 1 indoor unit be taken in to 41 F or upper using a duct heater In HEAT mode if temperature is out of range in the Use condition the fan of the Outside Air Unit intermittently operate So take care not to overheat a duct heater when use a duct heater Please refer to Outside Air Unit s Owner s Manual except the above contents 14 2 2 1 4...

Page 16: ...No operation of the remote control is accepted for a while after button is pushed While air conditioners are operated under the group control ALL is displayed first When is pushed the Indoor unit number displayed following ALL is the header unit 2 Each time button is pushed Indoor unit numbers in the control group change cyclically Select the Indoor unit to change settings for The fan of the selec...

Page 17: ...ield setting menu Push and hold the buttons for more than 4 seconds 3 Push the button to select 7 DN setting on the Field setting menu screen then push the Set F2 button The fan and louver of the indoor unit operate When the group control is used the fan and louver of the selected indoor unit operate Move the cursor to select Code DN with the F1 button then set Code DN with the button Move the cur...

Page 18: ...repeat from Procedure To change other settings of the selected Indoor unit repeat from Procedure Use button to clear the settings To make settings after button was pushed repeat from Procedure When button is pushed flashes and then the display content disappears and the air conditioner enters the normal stop mode While is flashing no operation of the remote control is accepted Display content vari...

Page 19: ... 2 75 Room A 12 00 Mode Fan Speed Cool Interface P C board SW17 1 Push the MENU button to display the menu screen 2 Push and hold the MENU button and the button at the same time to display the Field setting menu Push and hold the buttons for more than 4 seconds 3 Push the button to select 7 DN setting on the Field setting menu screen then push the Set F2 button The fan and louver of the indoor uni...

Page 20: ...U GRY G Y FM FAN1 GRY GRY WHI 4P GRY 4P WHI A BLK BLK ORN 1 2 ORN F1 F2 3 F3 F4 for Indoor Unit Control P C Board MCC 1403 CN061凚YEL 凚RED CN102 Sub P C Board TR1 凚WHI 凚YEL MCC 1520 CN01 T10 CN02 CN074凚WHI 凚GRN CN033 LM CN075 凚WHI Power circuit supply FS 凚RED CN030 凚YEL CN104 43F1 DRIVE FAN OPTION 凚RED CN060凚WHI CN082 CN103 凚GRN CN073 凚WHI CN032 CN101 凚BLK CN100 凚BRW 凚WHI 凚BLU 凚BLK CN081 FILTER PNL...

Page 21: ...1 YEL Control P C Board for Indoor Unit Line Filter Fuse T5 0A 250V F2 F1 FM2 8 WHI WHI RED RY005 RY006 UL L M H RY007 6 43F2 43F1 RY001 RY002 L2 L1 43F2 BLK ORN BLU FAN2 BLU 4P GRY RED WHI GRY RED WHI WHI RED WHI RED F2 F1 RED RED BLK BLK BLU BLU Unit Outdoor RC OC EMG BLU CN068 GRN CN033 LM FS RED CN030 YEL CN104 T10 CN075 WHI CN074 WHI CN050 WHI CN041 BLU CN040 BLU CN044 BRW CN066 WHI CN067 BLK...

Page 22: ...on FLA MCA A Model name MMD AP0481HF2UL MMD AP0721HF2UL MMD AP0961HF2UL Nominal Voltage V Ph Hz 208 230 1 60 MCA Minimum Circuit Amps FLA Full load Amps MOCP Maximum Overcurrent Protection Amps kW Fan Motor Rated Output kW 187 187 187 253 253 253 0 16 0 16 x 2 0 16 x 2 1 84 3 43 3 80 2 30 4 29 4 76 15 15 15 ...

Page 23: ... 㻝㻚㻢 㻠㻜㻜 㻡㻜㻜 㻢㻜㻜 㻣㻜㻜 External static pressure in WG Air flow rate cfm 㻝 㻝㻚㻝 㻝㻚㻞 㻝㻚㻟 㻝㻚㻠 㻝㻚㻡 㻝㻚㻢 㻝㻚㻣 㻝㻚㻤 㻝㻚㻥 㻞 㻠㻜㻜 㻡㻜㻜 㻢㻜㻜 㻣㻜㻜 Fan motor current A Air flow rate cfm Min 445 cfm Standard 636 cfm Min 445 cfm Standard 636 cfm Max 700 cfm Max 700 cfm Highstatic pressure tap Midstatic pressure tap Low static pressure tap Highstatic pressure tap Midstatic pressure tap Low static pressure tap Highstatic p...

Page 24: ...200 External static pressure in WG Air flow rate cfm 2 2 2 2 4 2 6 2 8 3 3 2 3 4 3 6 3 8 4 600 900 1200 Fan motor current A Air flow rate cfm Highstatic pressure tap Mid static pressure tap Low static pressure tap Highstatic pressure tap Mid static pressure tap Low static pressure tap Highstatic pressure tap Mid static pressure tap Low static pressure tap Highstatic pressure tap Mid static pressur...

Page 25: ...te cfm 0 0 2 0 4 0 6 0 8 1 1 2 1 4 1 6 800 1100 1400 External static pressure in WG Air flow rate cfm 2 2 2 2 4 2 6 2 8 3 3 2 3 4 3 6 3 8 800 1100 1400 Fan motor current A Air flow rate cfm Highstatic pressure tap Low static pressure tap Highstatic pressure tap Low static pressure tap Highstatic pressure tap Low static pressure tap Highstatic pressure tap Low static pressure tap MMD AP0961HF2UL Mi...

Page 26: ...50 500 1000 2000 4000 8000 Octave band center frequency Hz Octave band sound pressure level dB Audibility limits of continuous white level NC 50 NC 40 NC 30 NC 20 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Octave band center frequency Hz Octave band sound pressure level dB Audibility limits of continuous white level NC 50 NC 40 NC 30 NC 20 1 06 external static pressure in WG 0 16 0 86...

Page 27: ... level dB Audibility limits of continuous white level NC 50 NC 40 NC 30 NC 20 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Octave band center frequency Hz Octave band sound pressure level dB Audibility limits of continuous white level NC 50 NC 40 NC 30 NC 20 1 08 external static pressure in WG 1 00 0 65 0 84 external static pressure in WG 0 74 0 24 10 20 30 40 50 60 70 63 125 250 500 10...

Page 28: ...Outside Air Unit Type Engineering Data Book Model name MMD AP___1HF2UL May 2017 Third Edition ...

Reviews: