Filter sign setting

According to the installation condition, the filter sign 
term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

).

• For the CODE No. in Procedure 

3

, specify [01].

• For the [SET DATA] in Procedure 

4

, select the SET 

DATA of filter sign term from the following table.

To secure better effect of 
heating

When it is difficult to obtain satisfactory heating due to 
installation place of the indoor unit or structure of the 
room, the detection temperature of heating can be 
raised. Also use a circulator or other machinery to 
circulate heat air near the ceiling.
Follow to the basic operation procedure
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

).

• For the CODE No. in Procedure 

3

, specify [06].

• For the set data in Procedure 

4

, select the SET 

DATA of shift value of detection temperature to be 
set up from the following table.

Remote control sensor

The temperature sensor of the indoor unit senses room 
temperature usually. Set the remote control sensor to 
sense the temperature around the remote control.
Select items following the basic operation procedure 
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

 ).

• Specify [32] for the CODE No. in Procedure 

3

.

• Select the following data for the SET DATA in 

Procedure 

4

.

When 

 flashes, the remote control sensor is 

defective.
Select the SET DATA [0000] (not used) or replace the 
remote control.

Group control

In a group control, a remote control can control up to 
maximum 8 units.
• The wired remote control only can control a group 

control. The wireless remote control is unavailable 
for this control.

• For wiring procedure and wires of the individual line 

(Identical refrigerant line) system, refer to “Electrical 
connection” in this Manual.

• Wiring between indoor units in a group is performed 

in the following procedure.

• Connect the indoor units by connecting the remote 

control wires from the remote control terminal blocks 
(A, B) of the indoor unit connected with a remote 
control to the remote control terminal blocks (A, B) of 
the other indoor unit. (Non-polarity)

• For address setup, refer to the Installation Manual 

attached to the outdoor unit.

SET DATA

Filter sign term

0000

None

0001

150 H

0002

2500 H

(Factory default)

0003

5000 H

0004

10000 H

SET DATA

Detection temperature shift value

0000

No shift

0001

1.8 °F (+1 °C)

0002

3.6 °F (+2 °C)

(Factory default)

0003

5.4 °F (+3 °C)

0004

7.2 °F (+4 °C)

0005

9.0 °F (+5 °C)

0006

10.8 °F (+6 °C)

SET DATA

0000

0001

remote control 

sensor

Not used 

(Factory default)

Used

9

Test run

Before test run

• Before turning on the power supply, carry out the 

following procedure.

1) By using 500 V-megger, check that resistance 

of 1 M

 or more exists between the terminal 

block L

1

 to L

2

 and the earth (grounding).

If resistance of less than 1 M

 is detected, do 

not run the unit.

2) Check the valve of the outdoor unit being 

opened fully.

• To protect the compressor at activation time, leave 

power-ON for 12 hours or more before operating.

• Do not press the electromagnetic contactor to 

forcibly perform a test run. (This is very dangerous 
because the protective device does not work.)

• Before starting a test run, set addresses by following 

the Installation Manual supplied with the outdoor 
unit.

Execute a test run

Operate the unit with the wired remote control as usual.
For the procedure of the operation, refer to the 
attached Owner’s Manual to the outdoor unit.
A forced test run can be executed in the following 
procedure even if the operation stops by thermostat-
OFF.
In order to prevent a serial operation, the forced test 
run is released after 60 minutes have passed and 
returns to the usual operation.

CAUTION

Do not use the forced test run for cases other than the 
test run because it applies an excessive load to the 
devices.

Wired remote control

1

Push 

 button for 4 seconds or more. 

[TEST] is displayed on the display part and 
the selection of mode in the test mode is 
permitted.

2

Push  

button.

3

Select the operation mode with 

 

button, [

Cool] or [

Heat].

• Do not run the air conditioner in a mode other 

than [

Cool] or [

Heat].

• The temperature controlling function does not 

work during test run.

• The detection of error is performed as usual.

4

After the test run, push 

 button to 

stop a test run.

(Display part is same as procedure 

1

.)

5

Push 

 button to cancel (release from) the 

test run mode.

([TEST] disappears on the display and the status 
returns to a normal.)

2, 4

3

1,5

27-EN

28-EN

+00EH99881801_01EN.book  Page 14  Friday, November 25, 2011  10:23 AM

Summary of Contents for MMD-AP00244BH2UL

Page 1: ...L MMD AP0304BH2UL MMD AP0364BH2UL MMD AP0424BH2UL MMD AP0484BH2UL Indoor Unit Model name Medium Static Ducted Type MMD AP0074BH2UL MMD AP0094BH2UL MMD AP0124BH2UL MMD AP0154BH2UL MMD AP0184BH2UL MMD AP0214BH2UL AIR CONDITIONER MULTI TYPE Installation Manual 00EH99881801_01EN book Page 1 Friday November 25 2011 10 23 AM ...

Page 2: ...use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Connect ground wire grounding work Incomplete grounding may cause an electric shock Do not connect ground wires to gas pipes water pipes lightning rods or...

Page 3: ...oes not enter the refrigerating cycle To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the new refrigerant R410A For connecting pipes use new and clean piping designed for R410A and pleas...

Page 4: ...ncies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditioner or noise may adversely affect the equipment s operation Locations where there is anything under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation f...

Page 5: ... opening size C 23 6 600 41 3 1050 55 1 1400 Space required for attaching or detaching the filter D 23 6 600 23 6 600 40 5 1030 Electrical control box Air filter locally procured 5 9 150 Ceiling opening size 15 5 400 Min 1 Air discharge Ceiling opening size C Electrical control box Check port A 17 7 17 7 450 450 Air discharge 5 9 150 or more Air intake 1 2 30 Ceiling Ceiling Unit width 31 5 800 Ce...

Page 6: ...th plastic band at positions other than specified To install vibration isolation material to hanging bolts confirm that it does not increase the unit vibration External dimensions Unit in mm GOOD NO GOOD NO GOOD 1 room Hanging bolt 4 M0 4 10 locally procured Hanging bolt pitch B Unit external dimension A Air discharge flange outside C 5 5 140 1 7 44 1 9 49 Outside 8 6 218 2 5 8 147 5 Air filter sl...

Page 7: ...ir intake and air discharge sides are within 0 2 5 mm with each other Set the drain pipe connecting port side within 0 2 5 mm lower than opposite side Front view Side view 0 2 5 mm or less 0 2 5 mm or less Installation of wireless remote control sold separately For installation of the wireless remote control refer to the instructions that are supplied with the control The connection point for the ...

Page 8: ...emporarily with the screws indicated by the arrows for protection when shipped After reattaching it seal the screw holes with tape instead of using the screws Cover plate for filter slot Cover plate fixing screws 2 Pull out the filter rack and set the air filter locally procured in it 3 Push the filter rack in fully and reattach the cover plate Screws x 2 Filter rack Air filter locally procured Ai...

Page 9: ...leaks or if the condensate water does not flow normally the problem should be diagnosed and corrected before the system is certified for operation In the test run check that water drain is properly performed and water does not leak from the connecting part of the pipes When doing this also check that no abnormal sounds are heard from the drain pump motor Check draining also when installed in heati...

Page 10: ...rovided with the unit or the one used for the R410A refrigerant The flaring dimensions for R410A are different from the ones used for the conventional R22 refrigerant A new flare tool manufactured for use with the R410A refrigerant is recommended but the conventional tool can still be used if the projection margin of the copper pipe is adjusted to be as shown in the following table Projection marg...

Page 11: ... exothermic fire or malfunction 2 Connect ground wire grounding work Incomplete grounding cause an electric shock Do not connect ground wires to gas pipes water pipes lightning rods or ground wires for telephone wires 3 Install appliance in accordance with national wiring regulations Capacity shortage of circuit breaker or incomplete installation may cause an electric shock or a fire CAUTION Consu...

Page 12: ...of wireless type included Up to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor unit Indoor unit Indoor unit Remote control Max 8 units Remote control wiring CAUTION The remote control wire Communication line and AC208 230 V wires cannot be parallel to contact each other and cannot be store...

Page 13: ...ower has been turned on before the remote control becomes available for operations This is normal and is not indicative of trouble Concerning the automatic addresses The automatic addresses are set up by performing operations on the outdoor interface circuit board While the automatic addresses are being set up no remote control operations can be performed Setup takes up to 10 minutes usually about...

Page 14: ...the SET DATA of procedure 4 select a SET DATA of the external static pressure to be set up from the following table Change on wired remote control SET DATA External static pressure 0000 Standard Factory default 0001 High static pressure 1 0003 High static pressure 2 0006 Low static pressure With a remote control less system group control Besides the switching method using the wired remote control ...

Page 15: ...Filter sign term 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temperature shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA 0000 0001 remote control sensor Not used Factory default Used 9 Test run Before test run Before turning on the power supply carry out th...

Page 16: ...LOW or block the air vent Small screw Nameplate Notch M4 25 screw 2 pieces Spacer Receiver unit 10Troubleshooting Confirmation and check When an error occurred in the air conditioner the check code and the indoor UNIT No appear on the display part of the remote control The check code is only displayed during the operation If the display disappears operate the air conditioner according to the follo...

Page 17: ...ted units Capacity over No of connected indoor units Combined capacity of indoor units exceeds 120 of combined capacity of outdoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during autom...

Page 18: ...evice Wired remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 ...

Page 19: ...g systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22 lbs 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 33 lbs 15 kg NOTE 2 The standards for minimum room volume are as follows 1 No partition shad...

Page 20: ...IGH STATIC 1 0001 HIGH STATIC 2 0003 LOW STATIC 0006 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to Applicable controls in this manual Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE...

Reviews: