– 13 –
2
Each time
button is pushed, indoor
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs and the
louvers start swinging. The indoor unit for
change settings can be confirmed.
3
Specify CODE No. [
] with “TEMP.”
/
buttons.
4
Select SET DATA [
] with “TIME”
/
buttons.
5
Push
button. When the display changes
from flashing to lit, the setup is completed.
• To change settings of another indoor unit,
repeat from Procedure
2
.
• To change other settings of the selected indoor
unit, repeat from Procedure
3
.
Use
button to clear the settings. To make
settings after
button was pushed, repeat from
Procedure
2
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed,
flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While
is flashing, no operation of the
remote control is accepted.)
External static pressure
settings
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
procedure (
1
2
3
4
5
6
).
• Specify [5d] to the CODE No. in procedure
3
.
• For the SET DATA of procedure
4
, select a SET
DATA of the external static pressure to be set up
from the following table.
<Change on wired remote control>
SET DATA
External static pressure
0000
Standard (Factory default)
0001
High static pressure 1
0003
High static pressure 2
0006
Low static pressure
▼
With a remote control-less system (group control)
Besides the switching method using the wired remote control as a way to establish the external static pressure,
switching is also possible by changing over the DIP switch settings on the indoor P.C. board as shown in the
following table.
* However, once the settings are changed, it is necessary to reset the SET DATA to 0000 that placing the DIP
switch back to the factory default position and rewriting the SET DATA back to 0000 with wired remote control
(sold separately).
• Change over the DIP switch on the indoor P.C. board, and select the desired setting.
DIP switch positions (SW01, SW02)
DIP switch
position
SET DATA
0000
0001
0003
0006
External static
pressure
Standard
(Factory default)
High static Pressure 1
High static Pressure 2
Low static Pressure
SW02
SW02
SW01
SW02
OFF OFF
OFF OFF
1
2
ON
OFF
1
2
ON
OFF
SW01
SW02
OFF
ON
OFF OFF
1
2
ON
OFF
1
2
ON
OFF
SW01
SW02
OFF OFF
OFF ON
1
2
ON
OFF
1
2
ON
OFF
SW01
SW02
OFF
ON
OFF ON
1
2
ON
OFF
1
2
ON
OFF
25-EN
26-EN
+00EH99881801_01EN.book Page 13 Friday, November 25, 2011 10:23 AM