161
No. Component
Procedure
Remarks
⑪
Fan motor
replacement
1) Perform Step 1 of
①
, Step 1 of
②
, Step 2 of
⑤
.
2) Remove the flange nut fixing the fan motor and
propeller fan.
• Turn the flange nut clockwise to loosen it.
(To tighten it, turn it counterclockwise.)
3) Remove the propeller fan.
4) Remove the fan motor leads from the motor
base.
5) Hold the fan motor and remove the 4 fixing
screws so that the fan motor does not fall off.
6) Mount a new fan motor.
CAUTION
• Note that the wiring paths of the motor bases
(upper and lower) are different.
Also, make sure to arrange the lead wires
such that water cannot get inside the
mechanical compartment.
• Tighten the flange nut by 4.9 N•m
(50 kgf•cm).
• Adjust the length of the fan motor leads at
the inverter box to take up any excess slack
and ensure that the fan motor leads do not
come in contact with the propeller fan.
• Be careful so that the heat exchanger and
fan motor lead do not come into contact.
Flange nut
Turn the flange nut clockwise to loosen it.
Propeller fan
Fan motor (upper)
Hooks
(3 positions)
Fan motor (lower)
Hooks
(4 positions)