122
H03
H03
–
IPDU
Current
detection circuit
error
All stop
Current flow of at least
specified magnitude is
detected despite inverter
compressor having been shut
turned off.
• Check current detection
circuit wiring.
• Check defect in outdoor
P.C. board (A3-IPDU).
H04
H04
–
I/F
Compressor
case thermo
operation
All stop
Compressor case thermostat
performed protective
operation.
• Check compressor case
thermo circuit.
(Connector, wiring, P.C.
board)
• Check full opening of
service valve.
(Gas and liquid side)
• Check outdoor PMV
clogging.
• Check SV4 circuit leakage.
• Check miswiring /
misinstallation of SV4.
• Check valve open status of
indoor PMV.
• Check 4-way valve error.
• Check refrigerant amount
shortage.
H06
H06
–
I/F
Activation of
low-pressure
protection
All stop
Low-pressure Ps sensor
detects operating pressure
lower than 0.02 MPa.
• Check service valves to
confirm full opening
(both gas and liquid sides).
• Check outdoor PMV for
clogging.
• Check for defect in SV2 or
SV4 circuits.
• Check for defect in low-
pressure Ps sensor.
• Check indoor filter for
clogging.
• Check valve opening
status of indoor PMV.
• Check refrigerant piping for
clogging.
• Check operation of outdoor
fan (during heating).
• Check for insufficiency in
refrigerant quantity.
L03
–
–
Indoor
unit
Duplicated
indoor outdoor
unit
Stop of
corresponding
unit
There is more than one
outdoor unit in group.
• Check indoor addresses.
• Check for any change
made to remote controller
connection (group /
individual) since indoor
address setting.
L04
L04
–
I/F
Duplicated
outdoor line
address
All stop
There is duplication in line
address setting for outdoor
units belonging to different
refrigerant piping systems.
• Check line addresses.
L05
–
–
I/F
Duplicated
priority indoor
unit (as
displayed on
priority indoor
unit)
All stop
More than one indoor unit
has been set up as priority
indoor unit.
• Check display on priority
indoor unit.
L06
L06
No. of priority
indoor units
I/F
Duplicated
priority indoor
unit (as
displayed on
indoor unit other
than priority
indoor unit)
All stop
More than one indoor unit
have been set up as priority
indoor unit.
• Check displays on priority
indoor unit and outdoor
unit.
Location
of
detection
Description
System status
Error detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
Check code
• Check SV5 leak.
110