120
F01
–
–
Indoor
unit
Indoor TCJ
sensor error
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TCJ
sensor connector and
wiring.
• Check resistance
characteristics of TCJ
sensor.
• Check for defect in indoor
P.C. board.
F02
–
–
Indoor
unit
Indoor TC2
sensor error
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TC2
sensor connector and
wiring.
• Check resistance
characteristics of TC2
sensor.
• Check for defect in indoor
P.C. board.
F03
–
–
Indoor
unit
Indoor TC1
sensor error
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TC1
sensor connector and
wiring.
• Check resistance
characteristics of TC1
sensor.
• Check for defect in indoor
P.C. board.
F04
F04
–
I/F
TD sensor error All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TD
sensor connector.
• Check resistance
characteristics of TD
sensor.
• Check for defect in outdoor
P.C. board (I/F).
F06
F06
–
I/F
TE sensor error All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TE
sensor connectors.
• Check resistance
characteristics of TE
sensors.
• Check for defect in outdoor
P.C. board (I/F).
F07
F07
–
I/F
TL sensor error All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TL
sensor connector.
• Check resistance
characteristics of TL
sensor.
• Check for defect in outdoor
P.C. board (I/F).
F08
F08
–
I/F
TO sensor error All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TO
sensor connector.
• Check resistance
characteristics of TO
sensor.
• Check for defect in outdoor
P.C. board (I/F).
F10
–
–
Indoor
unit
Indoor TA
sensor error
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TA
sensor connector and
wiring.
• Check resistance
characteristics of TA
sensor.
• Check for defect in indoor
P.C. board.
F11
–
–
Indoor
unit
Indoor TF
sensor error
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TF
sensor connector and
wiring.
• Check resistance
characteristics of TF
sensor.
• Check for defect in indoor
P.C. board.
F12
F12
–
I/F
TS sensor error All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TS
sensor connector.
• Check resistance
characteristics of TS
sensor.
• Check for defect in outdoor
P.C. board (I/F).
Location
of
detection
Description
System status
Error detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
Check code
108