10
2
Equipment selection procedure
2-2.
Combination conditions for indoor unit and outdoor unit
Indoor unit can connect 50% to 135% of Outdoor unit capacity.
*MCY-MAP0367HS-UL is 80% to 135%.
2-2-1. The capacity code of indoor unit is decided for each capacity type.
2-2-2. For outdoor unit, maximum No. of connectable indoor units and total capacity code of
indoor units are decided.
Indoor unit capacity type
007 009 012 015 018 021 024 027 030 036 042 048
Indoor unit capacity code
7.5
9.5
12
15.4
18
21
24
27
30
36
42
48
Outdoor unit
Capacity code of outdoor unit
No. of connectable indoor units Total capacity code of indoor units
MCY-MAP0367HS-UL
36
2 to 6
18 to 48
MCY-MAP0487HS-UL
48
2 to 8
24 to 64
MCY-MAP0607HS-UL
60
2 to 9
30 to 81
E16-3P1_databook.book Page 10 Tuesday, December 20, 2016 3:02 PM