TIC-LF434H 

 

Introduction 

The electromagnetic flowmeter uses Faraday’s Law of 
electromagnetic induction to measure the process flow. 
The device consists of two units: a detector, through 
which the fluid to be measured flows and in which 
low-level signals proportional to flow rates are 
obtained; and a converter, which supplies excitation 
current to the detector, and amplifies the signals from 
the detector and then processes and converts the signals 
into the 4–20 mAdc current signal or communication 
signal. With the unique patented 

Mount-Anywhere

 

magnetic field distribution technology, the meter is 
highly immune to upstream flow disturbances. 
Combined with a multi-functional converter LF620 
(combined type) or LF622 (separate type) equipped 
with its patented 

Noise-Sentry

 original noise- 

suppression circuit and advanced 

algorithms

. The 

LF430 has a very high tolerance to noise, giving the unit 
a very stable output even for slurry fluid measurement. 
IR (Infrared) switches enable parameter setting of the 
converter without removing the cover. Flow direction 
can be set in either way, and its unique 128 x 128 dot 
matrix LCD display allows the LCD to be rotated 
electronically to 90, 180 and 270 degrees without 
opening the cover. The terminal block in LCD side 
make easy to wire in case of the combined type. 

*   HART protocol (Highway Addressable Remote Transducer) is a 

communication protocol for industrial sensors recommended 
by the HCF (HART Communication Foundation). 

 

** DevComm2000 Smart Device Communicator available 
through TIC for performing HART device configurations on 
PC or laptop. 

PROFIBUS is the communications protocol for factory and 
process automation that the PROFIBUS Organization 
recommends. Instead of analog control with a conventional 
analog signal (4-20 mA), it is fieldbus which digitizes all 
signals. Flowmeters support PROFIBUS-PA.

  

Modbus is the communication protocol that Modicon Inc. 
developed.  Physical layer is RS485. 

 

 

Figure1.  Configuration

 

 

 

  

 

 

LF430/LF620   

 LF430   

     LF622 

LF434/LF620F 

 LF434                   LF622F 

Figure2.  LF430 Mount-Anywhere series 

Flowmeters 

 

   

   

   

     

 

 

 

Specifications 

 

Overall Specifications 

Measurement range in terms of flow velocity: 

0

 

–1.0

 

ft/s to 0

 

 

32.8

 

ft/s (0

 

 

0.3

 

m/s to 0

 

–10

 

m/s) 

0

 

 

0.3

 

ft/s to 0

 

 

1.0

 

ft/s (0

 

 

0.1

 

m/s to 0

 

 

0.3

 

m/s) 

range is available as an option. 

Accuracy:  
< 1/2" to 18" ( 15mm to 450mm )> 

±

0.2 % of Rate

* This pulse output error result is established under standard 

operating conditions at Toshiba's flow calibration facility, 
Fuchu Japan. (NIST Traceable).  

* Individual meter measurement error may vary up to ±0.5% of 

Rate at 1.64 ft/s (0.5m/s) or more and ±0.3% of rate ±0.039 
inch/s (1mm/s) at 1.64 ft/s or less. 

* Current output: plus ± 8µA (0.05% of span.) 

* Refer to individual calibration data for each individual 

meter's measurement error. 

< 20" and 24" ( 500mm and 600mm )> 
 

±

0.3 % of Rate

*

 

* This pulse output error result is established under standard 

operating conditions at Toshiba's flow calibration facility, 
Fuchu Japan.  

* Individual meter measurement error may vary up to ±0.5% of 

Rate at 3.28 ft/s (1.0m/s) or more and ±0.3% of rate ±0.079 
inch/s (2mm/s) at 3.28 ft/s (1.0m/s) or less. 

* Current output: plus ± 8µA (0.05% of span.) 
* Refer to individual calibration data for each individual meter's 

measurement error. 

 

Field Intelligent Device – Mount Anywhere Series - Flanged 

Electromagnetic Flowmeter 

LF434 /LF620 
LF434 /LF622 

1/2" to 24" (15 to 600 mm) 

Cert. No. 

Z01207 

Combined type 

 

Separate type

 

Cert. No. PM09896 

For Hard rubber 

lined  flowmeter 

Summary of Contents for LF430/LF620

Page 1: ...communications protocol for factory and process automation that the PROFIBUS Organization recommends Instead of analog control with a conventional analog signal 4 20 mA it is fieldbus which digitizes all signals Flowmeters support PROFIBUS PA Modbus is the communication protocol that Modicon Inc developed Physical layer is RS485 Figure1 Configuration LF430 LF620 LF430 LF622 LF434 LF620F LF434 LF62...

Page 2: ...ange is required to maintain the specification performance Note The test results were obtained and demonstrated at TOSHIBA s flow calibration facility Fuchu Japan Drinking water approvals Hard rubber liner NSF Note Hard rubber liner is available from 4 to 24 Model LF430 and LF434 Detectors Mounting style Flange connection type Fluid pressure 15 psi or 1 0 bar 0 1 MPa to the nominal pressure of the...

Page 3: ...put non polarity Number of outputs One point Output capacity 150Vdc 150mA maximum or 150Vac peak to peak 100mA maximum Note DO2 cannot be used with the Modbus communication DO1 and DO2 functions One of the following functions can be assigned to DO1 std and or DO2 opt Pulse output available only for DO1 DO2 Pulse rate Max 10kHz 10 000pps DO1 Max 100Hz 100pps DO2 Over 1kpps auto setting Pulse width ...

Page 4: ... to 36Vdc 110Vdc allowable voltage 90 to 130Vdc Surge protection Arresters are installed in the power supply and a current signal output circuit to help protect the meter from lightning and improve personnel safety Case Aluminum alloy equal to IP 67 Coating Acrylic resin baked coating pearl gray colored Cable connection port Cable glands LF620 and LF622 without cFMus Approval Provided as standard ...

Page 5: ... 140 205 252 4 approx 5 0 25 160 208 265 4 approx 7 5 40 170 216 291 4 approx 9 5 50 180 225 308 4 approx 11 5 80 230 239 339 8 approx 16 5 100 240 257 367 8 approx 20 5 150 260 287 430 8 approx 36 0 200 300 313 483 12 approx 49 0 250 350 336 539 12 approx 105 300 400 363 593 12 approx 113 350 450 380 640 16 approx 130 400 500 401 684 16 approx 173 JIS 10K dimensions Meter size mm L1 mm L2 mm L3 m...

Page 6: ...ight kg 15 140 147 194 4 approx 4 0 25 160 149 207 4 approx 6 0 40 170 158 233 4 approx 9 0 50 180 167 250 4 approx 11 5 80 230 181 281 8 approx 17 5 100 240 199 309 8 approx 22 0 150 260 229 372 8 approx 37 0 200 300 255 425 12 approx 52 0 250 350 278 481 12 approx 108 300 400 305 535 12 approx 121 350 450 322 582 16 approx 145 400 500 343 633 16 approx 188 450 550 372 707 20 approx 208 JIS 10K d...

Page 7: ...OTE In the case of the integral type the signal line A B G and the excitation line E X Y are the connector joints Grounding with 100Ω or less ground resistance 1 Locate an external double pole power switch on the power line near the flowmeter within easy reach of operation Use the appropriate switch rating as shown below Switch rating 250Vac 6A or more In rush current 15A or more Figure 6 Combined...

Page 8: ...ed steel conduit Power switch External double pole power switch Figure 7 Separate type LF430 LF622 and LF434 LF622F flowmeters wiring Diagram Table 2 LF620 LF620F LF622 and LF622F Converters Signal Table Symbol Description Cable L1 Power supply Power cable CVV L2 GND Ground for arrester FG Frame ground DI Digital Input 20 30Vdc I O cable CVV S DO1 Digital Output 1 DO2 Digital Output 2 COM Signal C...

Page 9: ...ing nicked or damaged In addition for cables be careful of allowable maximum bend diameter Do not allow excessive twisting or bending of cables 5 Consider installing a PROFIBUS PA arrester in the communication path of PROFBUS PA so that the electromagnetic flowmeter will not be affected by lightning etc 6 The electromagnetic flowmeter is not equipped with terminating resistors Use the terminating ...

Page 10: ...354 450 18 2 500 4 366 20 000 26 029 500 20 3 000 4 244 25 000 26 354 600 24 4 000 3 930 40 000 29 283 Note The unit of gal min is not exchanged converted by m3 h About establishment environment Do not store or install the flowmeter Where there is direct sunlight Where excessive vibration or mechanical shock occurs Where high temperature or high humidity conditions exist Where corrosive atmosphere...

Page 11: ...0K Z Other Electrode Material Note 5 B 316L stainless steel C Ti titanium D Pt Ir platinum iridium E Ta tantalum F Hastelloy C Equivalent Z Other Lining Materials Note 5 C Teflon PFA 16 Note 8 Note 8 D E EPDM Rubber 3 18 Hard Rubber with NSF approval 4 24 Grounding Ring Material Note 5 C 316 stainless steel D 316L stainless steel E Ti titanium F Ta tantalum G Pt Ir platinum iridium H Hastelloy C E...

Page 12: ...l SUS304 Accessory for pipe installation BNP material SUS304 2 Digital input output Digital output points 2 DO1 DO2 Digital input point 1 DI 1 2 3 Current output and Communication function Current output HART communication PROFIBUS communication Current output is not functional Current output Modbus RS485 communication Digital outputs 2 DO1 DO2 and Digital 1 DI input are not functional 1 2 3 Power...

Reviews: