Introduction 

The LF502 electromagnetic flowmeter uses Faraday’s 

Law of electromagnetic induction in the same way as 

conventional electromagnetic flowmeters to measure 

the flow rate. Position of electrodes in the LF502 is so 

designed that it can be used even in a partially-filled 

pipe to measure the flow rate. 

Improved functional magnetic field distribution 

technique enables a high-precision flow measurement 

continually from low-level to fully-filled flow 

conditions. This

 

eliminates

 

unnecessary

 

piping

 

work

 

such

 

as

 

lifting the downstream pipe section to fill the 

detector pipe. 

Compared with flowmeters measuring the flow rate by 

means of flow level, the obstruction less LF502 

flowmeter does not usually allow mud, sands and other 

solid sediment stay at the bottom of the detector pipe 

and

 

is

 

unaffected

 

by

 

wave

 

or

 

floating

 

solids

 

on

 

the

 

fluid 

surface. 

The AF900 hand-held terminal (HART*

communicator) can be used to communicate with the 

flowmeter from a remote place.  

*1:  HART protocol (Highway Addressable Remote 

Transducer) is a communication protocol for industrial 

sensors recommended by the HCF

 

(HART

 

Communication

 

Foundation). 

 

 

Detector

 

Signal cable

 

Converter

 

Excitation cable 

Digital I/O

 

Power supply

4-20 mAdc 

 

Figure 1. LF502/LF232*F Configuration

 

 

 

 

Figure 2.  LF502 Electromagnetic Flowmeter 

for Partially-filled Pipes 

Specifications 

 

Overall Specifications 

Measurement range: 

Meter size 

Measurement range 

6” (150mm) 

0 – 264 GPM(std) to 0 – 1320 GPM 

(0 – 60 m

3

/h  to 0 – 300 m

3

/h ) 

8” (200mm ) 

0 – 484 GPM(std) to 0 – 2420 GPM 

(0 – 110 m

3

/h  to 0 – 550 m

3

/h ) 

10” (250mm ) 

0 – 770 GPM(std) to 0 – 3850 GPM 

(0 – 175 m

3

/h  to 0 – 875 m

3

/h ) 

12” (300mm ) 

0 – 1100 GPM(std) to 0 – 5500 GPM

(0 – 250 m

3

/h  to 0 – 1250 m

3

/h ) 

14” (350mm ) 

0 – 1540 GPM(std) to 0 – 7700 GPM 

(0 – 350 m

3

/h  to 0 – 1750 m

3

/h ) 

16” (400mm ) 

0 – 1980 GPM(std) to 0 – 9900 GPM 

(0 – 450 m

3

/h  to 0 – 2250 m

3

/h ) 

20” (500mm ) 

0 – 3124 GPM(std) to 0 – 15620 GPM 

(0 – 710 m

3

/h  to 0 – 3550 m

3

/h ) 

24” (600mm ) 

0 – 4400 GPM(std) to 0 – 22000 GPM 

(0 – 1000 m

3

/h  to 0 – 5000 m

3

/h ) 

Note:

 Above flow rate is almost 0 – 3.28 ft/s (std) to 0 – 

16.4 ft/s (0 – 1 m/s  to 0 – 5 m/s ) flow velocity.

 

Fluid-level range: 

Meter size 

Specification 

6” to 12” m 

(150 to 300m ) 

1-1/4”(30mm ) to fully-filled condition.

14” to 24” 

(350 to 600mm )

10% of inside tube diameter to 
fully-filled condition. 

Note:

 The fully-filled condition means a 100% of inside 

tube diameter.

 

Accuracy: 

±2% FS (when measurement range is 

standard) 

Note:

 

The accuracy is measured under standard 

operating

 

conditions

 

at

 

Toshiba's

 

calibration

 

facility. 

Electromagnetic Flowmeter for  
Partially-filled Pipes 

LF502/LF232*F

6” to  24” 

(

150

 

to

 

600

 

mm

 )

 

LF502

LF232*F

Summary of Contents for LF232*F Series

Page 1: ...ble Converter Excitation cable Digital I O Power supply 4 20 mAdc Figure 1 LF502 LF232 F Configuration Figure 2 LF502 Electromagnetic Flowmeter for Partially filled Pipes Specifications Overall Specifications Measurement range Meter size Measurement range 6 150mm 0 264 GPM std to 0 1320 GPM 0 60 m3 h to 0 300 m3 h 8 200mm 0 484 GPM std to 0 2420 GPM 0 110 m3 h to 0 550 m3 h 10 250mm 0 770 GPM std ...

Page 2: ... 2 male screw Applicable diameter 0 433 to 0 512 inch 11 to 13mm Model LF232 F converter Input signals Analog signal the voltage signal from detector proportional to process flow rate Digital input DI opt added when 9th digit of specification code is 3 Voltage level High level 20 to 30 V dc Low level 2 V dc or less Input resistance 2 7 kΩ Number of inputs 2 points DI1 and DI2 DI functions For digi...

Page 3: ... back light 2 units can be selected from the flowing units flow velocity instantaneous flow rate total flow forward reverse difference flow total count custom unit Parameter settings Parameters can be set as follows IR Switches Various parameters can be set without opening the converter housing using 4 infrared switches password can be set Zero adjustment Zero point adjustment can be started by pr...

Page 4: ...ate type LF502 Meter size 10 to 24 Roll prevention base Unit inch mm 3 46 88 1 57 40 1 42 36 5 63 143 4 96 126 11 81 300 Figure 4 Detector Dimensions for Meter Sizes 10 250 mm to 24 600 mm See the following tables for dimensions of L1 L2 and L3 in Figure 4 above and the number of bolts required for each flange ANSI 150 flange dimensions Meter Size inch L1 inch L2 inch L3 inch No of bolts Weight lb...

Page 5: ... けは パ ネ ル 壁 面 取 付 けか パイプ取付けで行います 指 定 され た取 付 用ボルト ナットが付 属します 2Bパイプ取付けの場合 2B 50mm パイプ M10 U ボルト 400 Excitation cable ground I O cable ground Signal cable ground Grounding terminal Output cable ground Power supply cable ground M10 U bolts In the case of 2B pipe installation 11 to 12 φhole 4 places Installation method Weight Approximately18 lb 8 kg including a mounting bracket 40 2 91 74 15 75 400 14...

Page 6: ...Grounding terminal at detector body and Grounding ring at upstream side Between Grounding terminal at detector body and Grounding ring at downstream side When the material of next pipes are non conductive like plastic use a 5 5mm2 or larger core cable for grounding of detector and wire 1 place as follows Between Grounding terminal at detector body and Grounding 100 ohm or less 4 DO1 to DO4 and DI1...

Page 7: ...ons exist Where corrosive atmospheres exist Places that can be submerged under water Where there is sloped floor To put the flowmeter temporarily on the floor place it carefully with something such as stopper to support it so that the flowmeter will not topple over In areas like the following there may be the case that infrared switches do not function correctly If these are unavoidable use an app...

Page 8: ...on Not available Size groups A 6 150mm to 16 400mm B 20 500mm and 24 600mm Table 2 Specification Code for LF232 F converter Model Specification Code 1 2 3 4 5 6 7 8 9 10 11 12 Contents LF232 type L F 2 3 2 Separate type converter A Purpose Standard F Compatible detectors For Partially filled pipes Meter size 150mm 6 to 600mm 24 C E Mounting nuts and bolts Panel wall mounting material 304 stainless...

Reviews: