CNU1/1A and CNU2/2A Pinout
Table 7. CNU1/1A and CNU2/2A pinout assignments.
Note:
For normal operation, connect CNU1 to CNU1A. Connecting CNU1 to CNU2A will
result in a failed communications condition indicated by a continuous splash screen
display. Connect CNU1 to CNU1A and continue normally.
See the 7-Series Communications Manual (P/N 53840) for more information on the
HX7+ ASD
communications protocol and system configuration requirements.
CN3 Pinout
CN3
is used for RS232/RS485 serial communications.
Table 8. CNU3 pinout assignments.
Pin #
CNU1 Pinout
(Control PCB)
CNU1A Pinout
(keypad)
Pin #
CNU2 Pinout
(Control PCB)
CNU2A Pinout
(keypad)
1
P24
P24
1
P24
P24
2
Gnd
Gnd
2
Gnd
Gnd
3
Tx (-)
RXA
3
Rx
Tx
4
Rx (+)
TXA
4
Gnd
Gnd
5
Rx (-)
TXB
5
Tx
Rx
6
Tx (+)
RXB
6
Gnd
Gnd
7
RS232/RS485
CNU3
7
Open
Open
8
Gnd
Gnd
8
Gnd
Gnd
Pin Number
CNU3 Pinout
(Control PCB)
1
RS232/RS485
2
RS232/RS485 Signal -
3
RS232/RS485 Signal Gnd
4
Shield
WARNING
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...