HX7+ ASD Installation and Operation Manual
Operation Above 60 Hz
A motor produces more noise and vibration when it is operated at frequencies above 60 Hz. Also, when
operating a motor above 60 Hz, the rated limit of the motor or its bearings may be exceeded; this may void
the motor warranty.
Contact the motor manufacturer for additional information before operating the motor above 60 Hz.
Power Factor Correction
DO NOT
connect a power factor correction capacitor or surge absorber to the three-phase output of the
HX7+ ASD
.
If the HX7+ ASD is used with a motor that is equipped with a capacitor for power factor correction,
remove the capacitor from the motor.
Connecting either of these devices to the output of the HX7+ ASD may cause the HX7+ ASD to
malfunction and trip, or the output device may cause an over-current condition resulting in damage to the
device or the HX7+ ASD.
Light Load Conditions
When a motor is operated under a continuous light load (i.e., at a load of less than 50% of its rated
capacity) or it drives a load which produces a very small amount of inertia, it may become unstable and
produce abnormal vibration or trips because of an over-current condition. In such a case, the carrier
frequency may be lowered to compensate for this undesirable condition (see
Program
Special Control
).
Note:
For proper operation, the carrier frequency must be 2.2 kHz or above except when
operating in the
Constant Torque
,
Variable Torque
, or the
5-Point Setting
modes.
Note:
See
for more information on setting the carrier frequency for normal operation
and for setting the carrier frequency above the derate threshold.
Motor/Load Combinations
When the
HX7+ ASD
is used in combination with one of the following motors or loads, it may result in
unstable operation.
•
A motor with a rated capacity that exceeds the motor capacity recommended for the HX7+ ASD.
•
An explosion-proof motor.
When using the HX7+ ASD with an explosion-proof motor or other special motor types, lower the carrier
frequency to stabilize the operation.
DO NOT
set the carrier frequency below 2.2 kHz if operating the
system in the vector control mode.
Note:
For proper operation, the carrier frequency must be 2.2 kHz or above except when
operating in the
Constant Torque
,
Variable Torque
, or the
5-Point Setting
modes.
•
If the motor that is coupled to a load that has a large backlash or a reciprocating load, use one of the
following procedures to stabilize its operation.
•
Adjust the
S-pattern
acceleration/deceleration setting,
•
If in the
Vector
control mode, adjust the response time, or
•
Switch to the
Constant Torque
control mode.
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...