[F08] Error TO sensor failure
[F10] Error TWI sensor failure
[F11] Error TWO sensor failure
Correct TO sensor
connection
Replace TO sensor
No
No
TO sensor
connector (CN602) is
connected
Yes
TO sensor
resistance characteristic
is normal
Yes
Start
Replace water heat exchange control board
(Refer to Characteristic table on page 113)
Correct TWI sensor
connection
Replace TWI sensor
No
No
TWI sensor
connector (CN205) is
connected
Yes
TWI sensor
characteristic is normal
Yes
Start
Replace water heat exchange control board
(Refer to Characteristic table on page 113)
Correct TWO sensor
connection
Replace TWO sensor
No
No
TWO sensor
connector (CN205) is
connected
Yes
TWO sensor
characteristic is normal
Yes
Start
Replace water heat exchange control board
(Refer to Characteristic table on page 113)