GX7R ASD Quick Start Guide
71
Cable/Terminal Specifications
Installation should conform to the latest release of the National Electrical Code Article 110 (NEC)
(Requirements for Electrical Installations), all regulations of the Occupational Safety and Health
Administration, and any other applicable national, regional, or industry codes and standards.
Note:
The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the ASD. Application-specific applicables, wire insulation
type, conductor material, ASD rating, and local and regional regulations are but a few
of the considerations when selecting the actual wire type and lug to be used with the
ASD.
Note:
Cable/Terminal specifications are based on the rated current of the ASD and
Do Not
include the 10% Service Factor.
Because the
GX7R ASD
may be commissioned within a wide range of environments and applications,
consider the application with each installation.
Cable specifications are to take full-load current and breaker lug accommodations into consideration.
Although the cable size recommendations take typical current ratings into consideration, the minimum
cable size may not be suitable for an application requiring a current load near the upper end of the cable
specification. Please consult the NEC for cable specifications appropriate for your application.
For further installation information on Cable/Terminal selection see the section titled
or contact your
Toshiba
Table 16. 480-Volt GX7R ASD Cable/Terminal Specifications.
Model
GX7R
MCP
Rating
(Amps)
Typical Wire/Cable Size (AWG or kcmil)
Lug Size Range
Input/Output Power
AM, FM, and II
Terminals
Control Terminals
Wire-Size/Lug-Capacity for
Input/Output Power
Recommended
Maximum
4300
75
6
4
20
(3-core shield)
18
(2-core shield)
6 – 500
4400
100
4
4
4550
100
3
2
4650
125
2
2
4850
175
1
**2
410K
200
2/0
2/0
413K
250
*1/0
*4/0
415K
300
*2/0
*4/0
Summary of Contents for GX7R ASD
Page 1: ...GX7R ASD Quick Start Guide TOSHIBA GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 2: ...GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 76: ...68 GX7R ASD Quick Start Guide Figure 23 480 Volt 30 100 HP GX7R ASD ...
Page 77: ...GX7R ASD Quick Start Guide 69 Figure 24 480 Volt 125 150 HP GX7R ASD ...