56
GX7R ASD Quick Start Guide
Alarms, Trips, and Troubleshooting
Alarms and Trips
This section lists the available
User Notification
codes of the EOI display and provides information that
assists the user in the event that a
Fault
is incurred. The
User Notification
codes are displayed as an
indication that a system function or system condition is active (i.e., ATN or DBON). The code is displayed
on the EOI for the duration of the activation.
If a user setting or an ASD parameter has been exceeded, or if a data transfer function produces an
unexpected result, a condition that is referred to as a
Fault
is incurred.
An
Alarm
is an indication that a
Fault
is imminent if existing operating conditions continue unchanged.
An
Alarm
may be associated with an output terminal to notify the operator of the condition remotely,
close a contact, or engage a brake. At the least, an
Alarm
will cause an alarm code to appear on the EOI
lists the
Alarm
codes that may be displayed during operation of the
GX7R
ASD
.
In the event that the condition that caused the
Alarm
does not return to its normal operating level within a
specified time, the ASD
Faults
and a
Trip
is incurred (Fault and Trip are sometimes used
interchangeably). A
Trip
is a safety feature, and is the result of a
Fault
, that disables the ASD system in
the event that a subsystem of the ASD is malfunctioning, or one or more of the variables listed below
exceeds its normal range (time and/or magnitude).
• Current,
• Voltage,
• Speed,
• Temperature,
• Torque, or
• Load.
See
for a listing of the potential
Trips
and the associated probable causes.
The operating conditions at the time of the trip may be used to help determine the cause of the trip. Listed
below are operating conditions that may be used to assist the operator in correcting the problem or that the
ASD operator should be prepared to discuss when contacting the
Toshiba
for
assistance.
• What is the ASD/Motor size?
• What trip information is displayed?
• Is this a new installation?
• Has the system ever worked properly and what are the recent modifications (if any)?
• Does the ASD trip when accelerating, running, decelerating, or when not running?
• Does the ASD reach the commanded frequency?
• Does the ASD trip without the motor attached?
• Does ASD trip with an unloaded motor?
• What is the CPU version and revision level?
• What is the EOI version?
Summary of Contents for GX7R ASD
Page 1: ...GX7R ASD Quick Start Guide TOSHIBA GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 2: ...GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 76: ...68 GX7R ASD Quick Start Guide Figure 23 480 Volt 30 100 HP GX7R ASD ...
Page 77: ...GX7R ASD Quick Start Guide 69 Figure 24 480 Volt 125 150 HP GX7R ASD ...