GX7R ASD Quick Start Guide
29
GX7R ASD EOI and Front Panel Features
The
GX7R
ASD Electronic Operator Interface
(EOI)
is comprised of an LCD display, two LEDs, a
rotary encoder, and eight keys. These items are described below and their locations are provided in
.
The EOI may be mounted remotely using the optional
ASD-MTG-KIT
. Or if operating in a
NEMA 4
environment, the
ASD-EOI-N4
is best suited for this application. Each kit contains all of the hardware
required to mount the EOI of the ASD remotely.
The EOI can be mounted remotely from the ASD as described in the
GX7R ASD Install and Op Manual
.
The dimensional requirements for remote mounting may also be found in this section. Using a screw
length that exceeds the specified dimensions may cause deformation of the outer surface of the bezel and
should be avoided.
The interface can operate up to distances of 15 feet from the ASD via the Common Serial (TTL) Port. For
distances beyond 15 feet, the RS232/RS485 port is recommended.
EOI Features
LCD Display
— Displays configuration information, performance data (e.g., motor frequency, bus
voltage, torque, etc.), and diagnostic information.
Enter Key
— Selects a menu item to be changed or accepts and records the changed data of the selected
field (same as pressing the
Rotary Encoder
).
Up Key
— Increases the value of the selected numerical parameter or scrolls up the menu listing
(continues during press-and-hold).
Down Key
— Decreases the value of the selected numerical parameter or scrolls down the menu listing
(continues during press-and-hold).
Rotary Encoder
— Functions as the
Up
key, the
Down
key, and the
Enter
key. Turn the
Rotary
Encoder
either clockwise or counterclockwise to perform the
Up
or
Down
key functions. Press the
Rotary Encoder
to perform the
Enter
function. Simultaneously press and turn the
Rotary Encoder
to
perform a user-defined function (see Program
EOI Option Setups
Preferences
).
ESC Key
— Returns to the previous level of the menu tree, toggles between the
and the
screens, or cancels changes made to a field if pressed while still in the reverse video
mode (dark background/light text). The three functions are menu-specific.
Stop Key
— While running, issues the
Off
command (decelerates to
Stop
at the programmed rate) if
pressed once while in the
Local
mode or initiates an
Emergency Off
(terminates the ASD output and
applies the brake if so configured) if pressed twice quickly from the
Local
or
Remote
modes. Resets the
ASD if pressed twice quickly while stopped.
Local|Remote Key
— Toggles the system to and from the
Local
and
Remote
modes. The LED is on
when the system is in the
Local Command
mode. The
Local
mode allows the
Command
and
Frequency
control functions to be carried out via the EOI.
The
Remote
mode enables the
Command
and
Frequency
control functions to be carried out via the
Terminal Board
,
CN8 Option
(Not Used),
RS232/RS485
,
Communication Card
,
or
Pulse Input
. The
selection may be made via Program
Fundamentals
Standard Mode Settings
The availability of the
Local
mode of operation (
Command
and
Frequency
control) may be disabled via
Program
EOI Option Setups
. The availability of the
Local
mode of operation
may be reinstated by changing this setting or performing a
Reset
(see
F007
).
ocal|Remote
Key
Summary of Contents for GX7R ASD
Page 1: ...GX7R ASD Quick Start Guide TOSHIBA GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 2: ...GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 76: ...68 GX7R ASD Quick Start Guide Figure 23 480 Volt 30 100 HP GX7R ASD ...
Page 77: ...GX7R ASD Quick Start Guide 69 Figure 24 480 Volt 125 150 HP GX7R ASD ...