14
6
F
2
S
0
7
8
9
2.3.2 Matching of CT Secondary Currents
In order to restrain erroneous differential currents, the currents supplied to the differential
elements must be matched in phase and amplitude under through-load and through-fault
conditions.
In GRT100, the matching is performed through the settings.
2.3.2.1 Matching of Phase Angle
It is necessary to compensate for phase angle difference among line currents on each side of the
transformer when the transformer windings have both star- and delta-connections.
GRT100 can compensate for the phase angle difference by the setting and does not require CT
secondary circuit arrangement such as delta-connection on the star-connected side of the power
transformer which was common for the former transformer protection.
The phase angle matching is performed by inputting the phase angle of each winding according
to the hands of a clock. For details of the setting, refer to 2.3.4.
2.3.2.2 Matching of CT Ratio
When I
1
to I
3
relevant to 1CT to 3CT
secondary currents are supplied, the differential current I
d
is
calculated employing the following equation,
I
d
= kct1
I
1
+ kct2
I
2
+ kct3
I
3
where kct1 to kct3 are settings corresponding to 1CT to 3CT.
The setting kct1 is obtained by using the following equation.
kct1 = I
n
/I
base1
= I
n
/( 3
I
base1
) if the 1CT is delta-connected.
where
I
n
= rated secondary current of the 1CT.
I
base1
= secondary current of the 1CT based on the kVA rating of the power transformer.
= transformer capacity(kVA)/( 3
rated voltage(kV) /CT ratio of 1CT
If the 1CT secondary circuit is delta-connected, 3
I
base1
is used instead of I
base1
in the equation
above.
The settings kct2 and kct3 are obtained in the same way.
The differential current I
d
is zero under through-load and through-fault conditions.
kct1
I
1
to kct3
I
3
are equal to the rated secondary current of each CT when the rated line
currents based on the kVA rating of the power transformer flow.
Summary of Contents for GRT100 Series
Page 142: ... 141 6 F 2 S 0 7 8 9 Appendix A Block Diagram ...
Page 144: ... 143 6 F 2 S 0 7 8 9 Appendix B Signal List ...
Page 159: ... 158 6 F 2 S 0 7 8 9 ...
Page 160: ... 159 6 F 2 S 0 7 8 9 Appendix C Variable Timer List ...
Page 162: ... 161 6 F 2 S 0 7 8 9 Appendix D Binary Output Default Setting List ...
Page 165: ... 164 6 F 2 S 0 7 8 9 ...
Page 166: ... 165 6 F 2 S 0 7 8 9 Appendix E Details of Relay Menu and LCD and Button Operation ...
Page 174: ... 173 6 F 2 S 0 7 8 9 Appendix F Case Outline Flush Mount Type Rack Mount Type ...
Page 179: ... 178 6 F 2 S 0 7 8 9 ...
Page 180: ... 179 6 F 2 S 0 7 8 9 Appendix G External Connections ...
Page 185: ... 184 6 F 2 S 0 7 8 9 ...
Page 200: ... 199 6 F 2 S 0 7 8 9 ...
Page 201: ... 200 6 F 2 S 0 7 8 9 Appendix J Return Repair Form ...
Page 205: ... 204 6 F 2 S 0 7 8 9 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 206: ... 205 6 F 2 S 0 7 8 9 ...
Page 207: ... 206 6 F 2 S 0 7 8 9 Appendix K Technical Data ...
Page 220: ... 219 6 F 2 S 0 7 8 9 ...
Page 221: ... 220 6 F 2 S 0 7 8 9 Appendix M Symbols Used in Scheme Logic ...
Page 224: ... 223 6 F 2 S 0 7 8 9 ...
Page 225: ... 224 6 F 2 S 0 7 8 9 Appendix N Implementation of Thermal Model to IEC60255 8 ...
Page 228: ... 227 6 F 2 S 0 7 8 9 ...
Page 229: ... 228 6 F 2 S 0 7 8 9 Appendix O IEC60870 5 103 Interoperability and Troubleshooting ...
Page 241: ... 240 6 F 2 S 0 7 8 9 Appendix P Modbus Interoperability ...
Page 255: ... 254 6 F 2 S 0 7 8 9 ...
Page 256: ... 255 6 F 2 S 0 7 8 9 Appendix Q Inverse Time Characteristics ...
Page 259: ... 258 6 F 2 S 0 7 8 9 ...
Page 260: ... 259 6 F 2 S 0 7 8 9 Appendix R Failed Module Tracing and Replacement ...
Page 266: ... 265 6 F 2 S 0 7 8 9 Appendix S Ordering ...
Page 269: ... 268 6 F 2 S 0 7 8 9 3 1 Oct 2 2017 Republished under spin off company ...
Page 270: ......