6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 947 -
5.4.6
Settings of binary input circuits
(i)
Setting table (IO_SLOT1) at IO#1 (Function ID: 200B01)
For the standard type being furnished
Setting item
Range
Unit
s
Contents
Default setting
value
Notes
Common
THRES_Lvl
Low / High
-
Determination of input threshold
Low
CMP_NUM
4 - 9
-
Number of times filtered
4
BI1
BI1_CPL
Off / On
-
Programmable binary input enable
Off
On Delay Timer
0.000 - 300.000
s
On delay timer value
0.000
Off Delay Timer
0.000 - 300.000
s
Off delay timer value
0.000
INVERSE-SW
Normal / Inverse
-
Binary signal inversion
Normal
BI2
BI2_CPL
Off / On
-
Programmable binary input enable
Off
On Delay Timer
0.000 - 300.000
s
On delay timer value
0.000
Off Delay Timer
0.000 - 300.000
s
Off delay timer value
0.000
INVERSE-SW
Normal / Inverse
-
Binary signal inversion
Normal
……
……
……
……
……
BI32
BI32_CPL
Off / On
-
Programmable binary input enable
Off
On Delay Timer
0.000 - 300.000
s
On delay timer value
0.000
Off Delay Timer
0.000 - 300.000
s
Off delay timer value
0.000
INVERSE-SW
Normal / Inverse
-
Binary signal inversion
Normal
For the variable type being furnished
Setting item
Range
Unit
s
Contents
Default setting
value
Notes
Common
THRES_Lvl
Low / High
-
Determination of input threshold
Low
THRES_Grp1
10 - 220
V
Threshold through BI1 to BI3
Applicable only in BI-2 module and
BIO-4 module
75
THRES_Grp2
10 - 220
V
Threshold through BI4 to BI6
Applicable only in BI-2 module and
BIO-4 module
75
THRES_Grp3
10 - 220
V
Threshold through BI7 to BI9
Applicable only in BI-2 module and
BIO-4 module
75
THRES_Grp4
10 - 220
V
Threshold through BI10 to BI12
Applicable only in BI-2 module and
BIO-4 module
75
CMP_NUM
4 - 9
-
Number of times filtered
4
BI1
BI1_CPL
Off / On
-
Programmable binary input enable
Off
On Delay Timer
0.000 - 300.000
s
On delay timer value
0.000
Off Delay Timer
0.000 - 300.000
s
Off delay timer value
0.000
INVERSE-SW
Normal / Inverse
-
Binary signal inversion
Normal
BI2
BI2_CPL
Off / On
-
Programmable binary input enable
Off
On Delay Timer
0.000 - 300.000
s
On delay timer value
0.000
Off Delay Timer
0.000 - 300.000
s
Off delay timer value
0.000
INVERSE-SW
Normal / Inverse
-
Binary signal inversion
Normal
……
……
……
……
……
BI12
BI12_CPL
Off / On
-
Programmable binary input enable
Off
On Delay Timer
0.000 - 300.000
s
On delay timer value
0.000
Off Delay Timer
0.000 - 300.000
s
Off delay timer value
0.000
INVERSE-SW
Normal / Inverse
-
Binary signal inversion
Normal
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......