6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 857 -
4.9.8
Setting
TPOS01(FunctionID:513001)
Setting items
Range
Unit
Contents
Default
Note
Commo n
TPOS-NELD
0 - 99
- Number of Event lock detect time
10
TPOS-TELD
1 - 99
s Timer of detect event lock
10
TPOS-TELR
1 - 99
s Timer of recovery from event lock
10
TPOS01-EN
Off / On
- TPOS01 switch for Device01
Off
Dev01
TPOS01-DEVNAME
[Preferred text] - item name of TPOS_Dev1
TPOS_Dev1
!
TPOS01-000NAME
[Preferred text] - state name of (0,0,0)state
Travelling0
!
TPOS01-001NAME
[Preferred text] - state name of (0,0,1)state
P1
!
TPOS01-010NAME
[Preferred text] - state name of (0,1,0)state
P2
!
TPOS01-011NAME
[Preferred text] - state name of (0,1,1)state
Travelling1
!
TPOS01-100NAME
[Preferred text] - state name of (1,0,0)state
P3
!
TPOS01-101NAME
[Preferred text] - state name of (1,0,1)state
Travelling2
!
TPOS01-110NAME
[Preferred text] - state name of (1,1,0)state
Travelling3
!
TPOS01-111NAME
[Preferred text] - state name of (1,1,1)state
Travelling4
!
TPOS01-UDFNAME
[Preferred text] - state name of undefined
Undefine
!
TPOS01-FLTNAME
[Preferred text] - state name of faulty
Faulty
!
TPOS01-DEVTYPE
switch / EDS
- Device Type
switch
TPOS01-P1NOPSG
[Preferred signal]
- P1 Normally Open Signal of Dev1
Not assigned
TPOS01-P1NOPSGI
Off / On
- Signal inverse or not
Off
TPOS01-P2NOPSG
[Preferred signal]
- P2 Normally Open Signal of Dev1
Not assigned
TPOS01-P2NOPSGI
Off / On
- Signal inverse or not
Off
TPOS01-P3NOPSG
[Preferred signal]
- P3 Normally Open Signal of Dev1
Not assigned
TPOS01-P3NOPSGI
Off / On
- Signal inverse or not
Off
TPOS01-SPPEN
Off / On
- Automatic event suppression function
Off
TPOS01-UDFEN
Off / On /
CHKONLY
- undefined pallet check function
Off
TPOS01-UDFTIM
0.1 - 100.0
s palette undefined check timer
30.0
TPOS01-FLTEN
Off / On /
CHKONLY
- faulty pallet check function
Off
TPOS01-FLTTIM
0.1 - 100.0
s palette faulty check timer
30.0
TPOS01-CTREN
Off / On
- control mode (control enable)
Off
TPOS01-CTRMENU
Off / On
- control by MENU enable
Off
TPOS01-CTRAHMI
DIR / SBO
- control action(Direct or SBO)by HMI
SBO
TPOS01-NSLBORD1
[Preferred signal]
-
select binary output read data(DataID)1 for no
direction command
5130018904011DC0
TPOS01-NSLBORD2
[Preferred signal]
-
select binary output read data(DataID)2 for no
direction command
5130018904011DC0
TPOS01-NSLBORD3
[Preferred signal]
-
select binary output read data(DataID)3 for no
direction command
5130018904011DC0
TPOS01-P1SLBORD
[Preferred signal]
-
select binary output read data(DataID) for P1
direction command
5130018A04011DC4
TPOS01-P2SLBORD
[Preferred signal]
-
select binary output read data(DataID) for P2
direction command
5130018A04011DC6
TPOS01-P3SLBORD
[Preferred signal]
-
select binary output read data(DataID) for P3
direction command
5130018A04011DC8
TPOS01-P1EXBORD
[Preferred signal]
-
execute binary output read data(DataID) for
P1 direction command
Not assigned
TPOS01-P2EXBORD
[Preferred signal]
-
execute binary output read data(DataID) for
P2 direction command
Not assigned
TPOS01-P3EXBORD
[Preferred signal]
-
execute binary output read data(DataID) for
P3 direction command
Not assigned
TPOS01-LGCTRCON
FixedLogic /
PLC
- Change logic about control condition
FixedLogic
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......