6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 792 -
Input
Output
Selection logic in TPOS01
Command
“Local-P1-Control”
TPOS01-P1
ILK
†
condition (“P1”) passed
ILK
†
bypassing
1≥
ICB_STATE
[
TPOS01-CTRAHMI
]
SBO
TPOS01 function (Function ID:
513001)
SBO
DIR
&
&
1≥
&
0.1s
0
t
0.6s
0
t
Either
“SBO mode” or “DIR mode”
(e.g.,
“ctlmodel” in IEC61850
*
)
“Automatic sequence control function (AQEQ)
§
” in progress
ASEQ_MULTI_SEL
Select condition
‡
“TPOS01_P1SL_BO_FL”
(513001
_
8A04011DC4)
Select
“Failed”
To BO connection
Select
“success”
To
“Wait for a command”
Select command
with ILK
†
condition
Operate command
with ILK
†
condition
For SBO operation
For DIR operation
To
“Wait for a next
command
”
Figure 4.9-9 Selection logic for P1-control at the IED locally in TPOS01
††
†Note: The ILK function provides the operation criteria for “P1-control”.
‡Note: A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.9-20
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††
Note: To identify the input/output signals of the other TPOS logics, see Table 4.9-6,
Output signal to BO
When the “select condition” signal is true, the TPOS01 function can issue a “Select success”
signal at the output-point “TPOS01_P1SL_BO_FL”.
Note: The signal “TPOS01_P1SL_BO_FL” is the same as the signal shown in Figure
4.9-3. If the input signal “Local-P1-Control” is not true, the TPOS01 function
returns to the “Wait for a command” stage.
(v)
Receiving “Select command P2-control” from the local-end.
Figure 4.9-10 outlines the reception of the select command ‘P2-control’ from the local-end.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......