6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 582 -
7
Note: A supervision of the Binary IO module can detect connection errors for BI circuits
.
8
Note: The “Common control” (CMNCTRL) function can test and check the operation-
direction of logic. When the user sets
Off
for scheme switch [
SCDEN
], operation of
the logic is blocked if the logic is running in the same operation-direction
compared with the previous operation-direction. Alternatively, if
On
is set for the
scheme switch, the logic is not blocked.
9
Note: The user must program the PLC logic for “Control hierarchy condition”. The user
must connect the “Control hierarchy condition” to the select condition logic using
the connection point “DPSY01IN_TMP_28”. For more information, see Chapter
Control and monitoring application: Control hierarchy. See PLC#3 of Table 4.2-8.
Note that the logic outputs are generated separately for both the Closing-
execution and the Open-execution.
(viii)
Signal name and number
Note: The user should note the meaning of the following abbreviations shown in column
“M/O” of each table:
“O” signifies that the signal is provided for optional use.
“M” signifies that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings are
used.
“N/A” signifies that the user cannot change the state of the signal.
Table 4.2-15 PLC connection points (Input point for PLC#1 user a configurable condition)
Signal Number
Signal Name
Description
M/O
511001 810201EE57
DPSY01IN_TMP_35
DPSY01 user configurable condition(PLC#1)
O
511001 810202EE57
DPSY02IN_TMP_35
DPSY02 user configurable condition(PLC#1)
O
Table 4.2-16 PLC connection points (Input point for PLC#2 operate command Closing)
Signal Number
Signal Name
Description
M/O
511001 820201EE5E
DPSY01IN_TMP_44
DPSY01 user configurable condition(PLC#2)
O
511001 820202EE5E
DPSY02IN_TMP_44
DPSY02 user configurable condition(PLC#2)
O
Table 4.2-17 PLC connection points (Input point for PLC#3 operate command Closing)
Signal Number
Signal Name
Description
M/O
511001 800201EE56
DPSY01IN_TMP_34
DPSY01 user configurable condition(PLC#3)
O
511001 800202EE56
DPSY02IN_TMP_34
DPSY02 user configurable condition(PLC#3)
O
Table 4.2-18 PLC connection points (Input point for operate condition logic)
Signal Number
Signal Name
Description
M/O
511001 800201EE65
DPSY01IN_TMP_40
DPSY01 user additional condition(PLC#1)
O
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......