6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 567 -
Table 4.2-12 PLC connection points (Input signal for ‘cancel’ condition)
Signal Number
Signal Name
Description
M/O
511001 800201EE69
DPSY01IN_TMP_46
DPSY01 user configurable cancel condition
O
511001 800202EE69
DPSY02IN_TMP_46
DPSY02 user configurable cancel condition
O
Table 4.2-13 PLC monitoring points (Output signal for ‘cancel’ condition)
Signal Number
Signal Name
Description
511001 8602011E95
DPSY01_CC_SS
DPSY01 cancel succeed
511001 8602021E95
DPSY02_CC_SS
DPSY02 cancel succeed
511001 8702011E96
DPSY01_CC_FS
DPSY01 cancel failed
511001 8702021E96
DPSY02_CC_FS
DPSY02 cancel failed
(v)
Setting name
Note: The “xx” within “DPSYxx” represents the DPSY function number. (e.g., if DPSY01
is considered, the “xx” is equal to “01”. The numbers used for “xx” can be
represented by either “01” or “02”.)
Table 4.2-14 Setting for ‘Cancel’ in DPSYxx
Setting Name
Description
Default
Setting item or value
DPSYxx-LGCNFFCT
Logic selector for cancel condition (DPSY01-02)
Fixedlogic
Fixedlogic / PLC
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......