6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1224 -
11.4.5
Editing data of the configuration
(i)
Common setting
When the “Common setting” item is selected on the start screen of the IEC 60870-5-103
configuration, the “Common setting” setting screen is displayed. Settings common to each
frame can be performed in this screen.
Setting file remark
The remark of the setting file is used for managing the version of the configuration data file.
A comment with the maximum of 12 characters can be entered in the box. The comment can
be viewed on the IED screen.
Remote operation valid time
When “Time-tagged message” or “Time-tagged measured” occurs during the period from the
receiving any command (which is provided by “General command” setting) to the setting
time of “Remote Operation valid time”, its COT is set to COT=12 (Remote operation). This
setting for the event is enabled when the COT=12 and COT=1 or 11 are checked in “Time-
tagged message” or “Time-tagged measurand” setting. The setting range of “Remote
Operation valid time” is 0 to 60000ms. The default setting is 4000ms. In the following case,
the “Time-tagged measurand” with COT=12 occurs.
Command
receive
t
Time tagged measurand with
COT=11, 12 checked occurs.
Remote operation valid time = T
R
[ms]
Figure 11.4-2 Time setting for the remote operation
Local operation valid time
When “Time-tagged message” or “Time-tagged measurand” occurs during the period from
the start of local operation (described in 11.4.5(ii)-7) to the setting time of “Local Operation
valid time”, its COT is set to COT=11 (Local operation). This setting for the event is enabled
when the COT=11 and COT=1 or 12 are checked in “Time-tagged message” or “Time-tagged
measurand” setting. The setting range of “Remote Operation valid time” is 0 to 60000ms.
The default setting is 4000ms. In the following case, the “Time-tagged message” with
COT=11 occurs.
Time tagged measurand with
COT=1, 11, 12 checked occurs.
t
Local operation valid time = T
L
[ms]
(Off-delay time after finish of local operation)
Start of
local operation
Finish of
local operation
Figure 11.4-3 Time setting for the local operation
Measurand period
This setting is used to set the transmission cycle (s) of Measurand frame. The setting range
is 0 to 60s. If no Measurand frame is provided by measurand setting, this setting is disabled.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......