Unblinded Groups Default
Introduction
Only two of the G3’s nineteen programming
groups are accessible (unblinded) to the user when the
G3 is first powered or is defaulted to factory settings. This document outlines the keystrokes
necessary to create a custom default setting that has unblinded all programming groups except the
macros.
Programming
Group
Parameter
Value
UTILITY PARAMETERS
Standard Setting Mode Selection
3
UTILITY PARAMETERS
Blind Function Selection
1
UTILITY PARAMETERS
Fundamental Parameters #2 Blind
1
UTILITY PARAMETERS
Panel Control Parameters Blind
1
UTILITY PARAMETERS
Terminal Selection Parameters Blind
1
UTILITY PARAMETERS
Special Control Parameters Blind
1
UTILITY PARAMETERS
Frequency Setting Parameters Blind
1
UTILITY PARAMETERS
Protection Function Parameters Blind
1
UTILITY PARAMETERS
Pattern Run Control Parameters Blind
1
UTILITY PARAMETERS
Feedback Control Parameters Blind
1
UTILITY PARAMETERS
AM/FM Adjustment Blind
1
UTILITY PARAMETERS
Motor Parameters Blind
1
UTILITY PARAMETERS
Standard Setting Mode Selection
5
After this programming is completed, the drive will be set to Toshiba factory defaults and all the
programming groups except the macros will be unblinded.
At any time, to reset the drive back to Toshiba defaults
with the groups unblinded
, put a “6” in
Standard Setting Mode Selection in the UTILITY PARAMETER group.
At any time, to reset the drive back to Toshiba defaults, put a “3” in Standard Setting Mode Selection
in the UTILITY PARAMETER group.