9
6 F 2 S 0 8 7 7
Table 3.2.1 Default Setting of Configurable LED
LED
Name
Colour
Comment
LED1
-
-
-
LED2
-
-
-
LED3
TEST
Yellow
Lit whenTest Mode is selected.
LED4
LAN CONN FAIL
Yellow
Lit when LAN connection fails.
LED5
-
-
-
LED6
TIME SYNC LOSS
Yellow
Lit when synchronisation with SNTP is lost.
LED7
RS485-1 FAIL
Yellow
Lit when HDLC communication fails.
LED8
RS485-2 FAIL
Yellow
Lit when IEC-103 communication fails.
LED9
DB WRITING FAIL
Yellow
Lit when errors are detected in the data written by IFU
engineering tool.
LED10 -
-
-
LED11 -
-
-
LED12 -
-
-
2.3.3 Operation Mode
G1IF4 has two operation modes: on-line mode and test mode.
On-line mode is the normal operation mode. In Test mode, a test flag is added to all transmission
signals from relays.
2.3.4 Automatic Supervision
The automatic monitoring function detects failures that might occur within G1IF4. The
following items are monitored by the automatic supervision function:
- Binary input and output circuits
- Communication circuits for the station LAN, IEC60870-5-103 transmission network
- Processor (Watch Dog timer)
- Memory
- DC power supply circuit
When failures are detected by automatic monitoring, the "ALARM" LED on the front panel is
turned on and also detailed failure information is transmitted to station level control equipment
as event data.
The failure of the interface unit is indicated on the workstation at the station level, and its details
are also displayed on the local HMI.
2.3.4.1 Memory monitoring
The memories are monitored as follows depending on the type of memory:
Random access memory monitoring:
Writes/reads prescribed data and checks the storage function.
Program memory monitoring: Checks the checksum value of the written data.
Setting value monitoring:
Checks discrepancy between the setting values stored in
duplicate.
Summary of Contents for G1IF4
Page 29: ... 28 6 F 2 S 0 8 7 7 4 2 9 Active group Active group Group 1 fixed ...
Page 34: ... 33 6 F 2 S 0 8 7 7 IFU side setting ...
Page 35: ... 34 6 F 2 S 0 8 7 7 And then check the connecting status by RSM100 ...
Page 48: ... 47 6 F 2 S 0 8 7 7 Appendix A External Connections ...
Page 50: ... 49 6 F 2 S 0 8 7 7 Appendix B Outline Diagram ...
Page 52: ... 51 6 F 2 S 0 8 7 7 Appendix C Signal List ...
Page 103: ... 102 6 F 2 S 0 8 7 7 ...
Page 104: ... 103 6 F 2 S 0 8 7 7 Appendix D Setting Sheet 1 Relay Unit Identification 2 Default setting ...
Page 118: ... 117 6 F 2 S 0 8 7 7 Appendix E Return Repair Form ...
Page 121: ... 120 6 F 2 S 0 8 7 7 ...
Page 122: ... 121 6 F 2 S 0 8 7 7 Appendix F Technical Data ...
Page 125: ... 124 6 F 2 S 0 8 7 7 ...
Page 126: ... 125 6 F 2 S 0 8 7 7 Appendix G Ordering ...
Page 129: ......