Virtual Linear Pump Setup
https://www.toshiba.com/tic/
63
Virtual Linear Pump Setup
Toshiba’s Virtual Linear Pump algorithm allows for
direct and precise control of pressure, flow rate, or
level. This section provides useful setup and
operational information for the Virtual Linear Pump
system.
The system is initially configured using the
(Program
Virtual Linear Pump
) Setup Wizard.
Once the Wizard is started, it must be completed for
normal Virtual Linear Pump operations to function.
Note:
Do not run the VLP Wizard and the
Standard Start Up Wizard. Running
both will result in an operational
conflict that will require a reset to
factory defaults and a restart using
only one wizard. Reset to the factory
default settings after running either
wizard to run the other wizard.
The parameters addressed while using the Virtual
Linear Pump
Setup Wizard or the Virtual Linear
Pump
Settings
menu selections are also
accessible via the applicable associated direct
access numbers for specific adjustments when
required.
If not using the Wizard to configure the settings of
the Virtual Linear Pump algorithm, parameter
must first be set to 255: Setup to accept changes to
the Virtual Linear Pump parameter settings. Upon
completion of the parameter changes, set
parameter
to 1: Direct Mode or 2: Process
Hold to use the new settings for normal Virtual
Linear Pump operations (Zero may be selected at
to save the changes to be used later).
The setup procedure and the VLP Setup Wizard
setup screens are shown below.
Figure 30. Input the electrical specifications to the motor.
1. Enter the
FLA from the nameplate of the motor.
2. Select Pressure, Flow, or Level.
3. Select the command source; EOI, V/I, RR, Com.
Opt.
4. Set the Low Frequency Limit. 15 Hz fits most
applications.
5. Click Next to continue.
Figure 31. Input the specifications to the transducer.
1. Select the unit of measure for the transducer;
pressure, flow rate, or level (i.e., PSI, GPM,
Inches of Water Column, or Cubic Feet per Min
-
ute, °C, °F, or Custom).
2. Select the transducer output range and signal
type; current or voltage.
3. Select the maximum reading of the transducer.
4. Select the minimum reading of the transducer.
5. Click Next to continue.
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......