background image

BN interface

Installation Manual

9-

EN

Example of System Wiring Connections

7&&/,1.

9'&,1

(WKHUQHW/$1

䣒䣑䣙䣇䣔

䣖䣅䣅䢯䣎䣋䣐䣍

䣅䣒䣗

(5525

+8%

8

8

8

8

8

8

8

8

8

8

8

8

BN interface

Building Management System

Power adapter Power Supply

TCC-LINK main bus

Outdoor unit

Outdoor unit

Indoor unit

Indoor unit

Remote 
controller

Remote 
controller

Summary of Contents for BMS-IFBN640TLE

Page 1: ...English BN interface Model name BMS IFBN640TLE Installation Manual ...

Page 2: ...n 6 2 Power and signal line connections 8 3 Settings 10 3 1 Switch setting 10 3 2 LED 11 4 Factory default settings 11 5 Test run 12 5 1 BACnet communication settings 12 5 2 Setting up equipment data in the indoor unit 12 5 3 Cause of problem occurring during setup 13 6 Turning off the BN interface 13 ...

Page 3: ...es damage extending to buildings household effects domestic livestock and pets indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol indicates compulsory mandatory items The actual contents of the obligation are indicated by a picture or text placed inside or next to the graphic symbol Warning Installation a...

Page 4: ...le Pin terminal 2 TCC LINK caulked connectors Mounting bracket DIN rail 1 Use screws to secure the unit in locations without DIN rails walls etc Screws M4 x 12 2 For securing the DIN rails Rubber feet 4 For levelling the unit Screws M3 x 8 4 For securing the rubber feet to the unit CD R 1 Manual Installation Manual 1 This manual Tie wrap 1 Power supply Rated voltage 220 240 VAC 50 60 Hz Power cons...

Page 5: ... use Component Names Name Function 5V DCIN Connect the power adapter USB For service Ethernet LAN Connect to the Building Management System Shutdown button Shutdown or switch to air conditioning search mode L1 BACnet communication status indicator L2 BACnet communication status indicator setting error indicator 722 1 12 68 s s s s 䣒䣑䣙䣇䣔 䣖䣅䣅䢯䣎䣋䣐䣍 䣅䣒䣗 5525 86 9 1 WKHUQHW 1 6KXWGRZQ EXWWRQ ...

Page 6: ...to mount the unit or wall mount or surface mount it as shown below Use the supplied mounting bracket to wall mount or surface mount the interface 3 Surface mount Use screws to secure the supplied rubber legs to the interface before surface mounting it 1 DIN rail mount Install the interface on DIN rails mounted on a switchboard or elsewhere Front view Back view 2 Wall mount Use screws to attach the...

Page 7: ...ual 7 EN Installation Space and Maintenance Space A side space for connecting through cable inlets and an upper space for maintenance must be reserved before installation The other sides can be adjacent to surrounding objects PP PP ...

Page 8: ...TCC LINK communication cable connection No Line Description 1 For TCC LINK Type 2 core shielded wires Wire size 1 25 mm2 1000 m max total length including air conditioner wiring length Length 2 00 mm2 2000 m max 2 For Ethernet Type LAN cable higher than Category 5 UTP The appropriate use of straight cable cross cable should be done depending on your system used Length 100 m max 50 10 Connect the s...

Page 9: ...Wiring Connections 7 1 9 1 WKHUQHW 1 䣒䣑䣙䣇䣔 䣖䣅䣅䢯䣎䣋䣐䣍 䣅䣒䣗 5525 8 8 8 8 8 8 8 8 8 8 8 8 8 BN interface Building Management System Power adapter Power Supply TCC LINK main bus Outdoor unit Outdoor unit Indoor unit Indoor unit Remote controller Remote controller ...

Page 10: ...onditioning search mode function button Use this button to stop BACnet process and network process of the BN interface or to start up in the air conditioning search mode Note that button operation changes depending on how long it is depressed Time duration button is depressed Operation Less than 4 seconds Stop BACnet process and network process of the BN interface 4 seconds or more Starts air cond...

Page 11: ...cator in the BN interface L1 Green BACnet communication status indicator L2 Red BACnet communication status indicator setting error indicator 38 7 1 32 5 5525 䣒䣑䣙䣇䣔 䣖䣅䣅䢯䣎䣋䣐䣍 䣅䣒䣗 5525 䣒䣑䣙䣇䣔 䣖䣅䣅䢯䣎䣋䣐䣍 䣅䣒䣗 5525 No Item Factory default setting 1 IP address IP address 192 168 1 100 Subnet mask 255 255 255 0 2 UDP port 47808 0xBAC0 3 Device object instance number 100 4 Address setting switch 1 5 Test swi...

Page 12: ... on all indoor and outdoor units Set up as follows waiting 10 minutes after turning on all the units Setup work Turn on the BN interface When 10 minutes has elapsed since turning on the BN interface hold down the shutdown button for 4 seconds or longer L1 LED goes on When the BN interface has started up normally start reading the equipment data of the interface unit During this operation L1 LED wi...

Page 13: ... indoor and outdoor units are being initialized and it is not possible to communicate with them TCC LINK LED does not blink at all Make sure that indoor and outdoor units are turned on Make sure they have been on for at least 10 minutes The TCC LINK cables have been incorrectly connected Connect the cables correctly The centralized control address has not been set in the indoor units Make sure tha...

Page 14: ...DEA6709101 ...