4400 Series Installation and Operation Manual – 64527-008
11.2 Estimated Runtime on Internal Batteries – 15-30kVA
Following are charts of the estimated runtime for the 4400 Series 15, 20, 25, and 30kVA on internal batteries at various loads at a 0.8 and 0.9 Power
Factor.
These runtimes are estimates based on new batteries operating at 76 °F. Actual runtimes may vary due to manufacturing variations, previous discharge
profiles, battery age, and operating temperature.
ESTIMATED RUNTIME ON INTERNAL BATTERIES AT VARIOUS LOADS – 0.8 PF
1
UPS
Estimated Runtime in Minutes at Percent Full Load
1
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
15kVA (0.8 PF)
>60
>60
49
34
26
20
17
14
11
10
20kVA (0.8 PF)
>60
56
37
25
18
14
10
8
7
6
25kVA (0.8 PF)
>60
45
27
17
13
9
8
6
4
4
30kVA (0.8 PF)
>60
36
19
13
9
7
5
3
2
2
1 – Subject to change without notice.
ESTIMATED RUNTIME ON INTERNAL BATTERIES AT VARIOUS LOADS – 0.9 PF
1
UPS
Estimated Runtime in Minutes at Percent Full Load
1
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
15kVA (0.9 PF)
>60
>60
43
28
22
18
14
12
9
8
20kVA (0.9 PF)
>60
49
31
20
15
11
9
7
6
5
25kVA (0.9 PF)
>60
39
22
15
10
8
6
4
3
3
30kVA (0.9 PF)
>60
30
17
11
8
6
4
3
2
1
1 – Subject to change without notice.
11.3
15-30kVA Specifications – w/ External
Battery Backup
4400 SPECIFICATIONS: 15–30kVA w/ External Battery Backup
Specification
15kVA
20kVA
25kVA
30kVA
General
Model Number
4400X3X150XA
4400X3X200XA
4400X3X250XA
4400X3X300XA
Capacity Output
15 kVA (13.5kW)
20 kVA (18kW)
25 kVA (22.5kW)
30 kVA (27kW)
Topology
Double conversion all-IGBT UPS
Input
Voltage (V)
Nominal (Xfmr.) Input V10% to -15% (Intermittently to -30% at 70% load
1
), 3P/4W
+GND or 3P/3W + GND
Key
Transformer Voltage
Key
Transformer Voltage
A
200V Iso Xfmr
M
380V Iso Xfmr
B
208V Iso Xfmr
N
400V Iso Xfmr
C
220V Iso Xfmr
P
415V Iso Xfmr
D
230V Iso Xfmr
Q
230/133V Auto-Xfmr
E
240V Iso Xfmr
R
240/139V Auto-Xfmr
F
208/120V (No Xfmr)
S
480V Iso Xfmr
G
220/127V Auto-Xfmr
T
(Undefined)
H
380/220V Auto-Xfmr
U
600/347V Auto-Xfmr
I
400/230V Auto-Xfmr
V
600V Iso Xfmr
J
415/240V Auto-Xfmr
X
Not Used
K
480/277V Auto-Xfmr
Z
200/115V Auto-Xfmr