118
4400 Series Installation and Operation Manual – 64527-008
Appendix C – Installation Planning Guide
TOSHIBA
4400 UPS
Installation Planning Guide for
15-100kVA UPS
Standard System: 208/120V Input, 208/120V Output
Rev.
1
.6
Page 1 of 3
4400-
IPG
-208/120v-208/120V
General Mechanical Information
UPS kVA/ kW
Rating
Dimensions
(W x D x H)
Weight
Bare (w/ Int Batt.)
Approximate Full-
Load Heat Loss
Mechanical Clearance for Ventilation
and Maintenance Access
Inches
Lbs.
kBtu/Hr
15 kVA/ 13.5 kW
20
.12
x 37.
4
x 65.06
7
25 (1015)
4.6
Top:
16 in
(406 mm)
Front:
36 in
(900 mm)
Bottom/
Sides/
Back:
0 in.
(0 mm)
20
kVA/ 22.5 kW
20
.12
x 37.
4
x 65.06
7
30 (1020)
6.1
25 kVA/ 22.5 kW
20
.12
x 37.
4
x 65.06
7
50 (1035)
7.6
30 kVA/ 27 kW
20
.12
x 37.
4
x 65.06
7
60 (1045)
9.1
50 kVA/ 45 kW
32
.1
x 3
7.2
x 7
3.8
965 (1920)
15.2
80 kVA/ 72 kW
32
.1
x 3
7.2
x 7
3.6
1550 (N/A)
2
4.3
100 kVA/ 90 kW
32
.1
x 3
7.2
x 7
3.6
1650 (N/A)
30.4
Primary AC Input (208/120V 3-Phase / 4-Wire)
Power Demand at 100% Load
Suggested External
Feeder Breaker
Suggested Minimum Feeder Wire Size
Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
>0.99
42 (57
)
90 A
(1
) x
4
AWG / (1) x
2
AWG
380
20
>0.99
56
(71
)
125 A
(1) x
2
AWG
/ (1
)
x 2
AWG
380
25
>0.99
70 (85
)
150 A
(1) x 2 AWG
/ (1
)
x 2
AWG
380
30
>0.99
84 (99
)
175 A
(1) x 2 AWG
/ (1
) x 2 AWG
380
50
>0.9
9 140 (154
)
250 A
(1) x
4/0
AWG
/ (1
)
250 kcmil
380
80
>0.99
224 (239
)
400 A
(2
) x
2
/0 AWG
–
(1) x
500 kcmil /
(2)
x 350 kcmil
380
100
>0.99
280 (295
)
500 A
(2) x 4/0 AWG
–
(1) x 600 kcmil /
(2) x 5
00 kcmil
380
Bypass AC Input (208/120V 3-Phase / 4-Wire)
Power Demand at 100% Load
Suggested External
Feeder Breaker
Suggested Minimum Feeder Wire Size
Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
0.9
42
70 A
(1
) x 6 AWG / (1) x 2 AWG
380
20
0.9
56
90 A
(1) x 3 AWG
/ (1
) x 2 AWG
380
25
0.9
69
110 A
(1) x 2 AWG
/ (1
) x 2 AWG
380
30
0.9
83
150 A
(1) x 2 AWG
/ (1
) x 2 AWG
380
50
0.9
139
225 A
(1) x
4/0 / (1
)
250 kcmil
380
80
0.9
222
350 A
(2) x 2/0 AWG
–
(1
) x
400 kcmil /
(2)
x 300 kcmil
380
100
0.9
278
450 A
(2) x 3/0 AWG
–
(1) x 600 kcmil /
(2) x 500 kcmil
380
Battery Backup (288VDC Nominal)
Battery Capacity Required
for Full Load Output
Maximum Discharge
at Full Load Output
Suggested External
Feeder Breaker
1
Suggested Minimum Feeder
Wire Size Per
Polarity
Suggested Maximum
Feeder Length For Min. Wire
Size in Steel Conduit
kVA
kWB
Amps DC
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
1
4.7
64
A
100 A
(1
) x
2
AWG
70
20
19.6
85 A
150 A
(1
) x
2
AWG
70
25
2
4.5
107 A
175 A
(1
) x 2 AWG
70
30
29.4
128 A
200 A
(1
) x 2 AWG
70
50
49.5
215 A
350 A
(1
) x
250 kcmil
70
80
79.2
344 A
6
00 A
(2) x 250 kcmil
70
100
98.9
430 A
700 A
(2) x 350 kcmil
70
1
–
External overcurrent overprotection not needed if
battery cabinet(s) are each equipped with an appropriate internal circuit breaker
2
–
External feeder cables may change depending on number of battery cabinets placed in parallel.
3
–
Feeder ampacity based on worst case
temperature conditions and sized to be protected by overcurrent device.