4400 Series Installation and Operation Manual – 64527-008
4400 System Status Messages
Display
Meaning
Action
EE1ST
EEPROM is loaded with default
values.
No action needed.
EPO
EPO circuit is active.
Reset
EPO switch to start.
EQCHRG
Equalized Charging
No action needed.
FLT
A fault has occurred.
See Fault records.
FRCDBYP
UPS forced into bypass mode.
Secure the load and contact the nearest Toshiba
authorized representative for service.
FWUPD
Firmware updated.
No action needed.
INVSTUP
UPS starts up in inverter mode
(skips bypass)
No action needed.
INV
Inverter mode.
Inverter is running (it can be On-Line, Battery Test, or
Backup)
LANSD
UPS goes to Shutdown triggered
from LAN SD (shutdown) circuit.
Deactivate LAN
shutdown signal to reset.
LB
Low
Battery – The battery volt
-
age has dropped low (about 90%
or less) during operation. Con
-
tinued operation in this mode will
deplete battery and cause output
shut down. (This can be adjusted
by the operator
Immediately shut down the load equipment in an
orderly fashion and then press the STOP key.
LCRUN
Local run command issued.
No action needed.
MANUAL
UPS is in Manual mode
No action needed.
OUT50HZ
UPS set for 50 Hz Output.
No action needed.
PFAIL
Input power failure.
No action needed.
PRCHRG
Protective charging
No action needed.
RMRUN
Remote Run command issued.
No action needed.
RMTSD
Remote shutdown occurred.
One or more warnings occurred. Check the Warnings
field for details. Disconnect LAN signal to reset.
RMTSWEN
Remote switch control enable.
No action needed.
SYN
Synchronous mode.
Input and output are synchronized.
TIMEDSD
UPS is counting down prior to
shutdown.
Immediately shut down the load equipment in an
orderly fashion and then press the STOP key.
WRN
A warning has occurred.
See Warning record.