10.8 Battery Test
The 1600XP/1600XPi allows the user to conduct automatic or manual battery tests as desired. The
following steps detail the battery test procedures.
Automatic Battery Test:
1.
The Automatic Battery Test Procedure is performed only if it is enabled during startup.
2.
Once the battery test is completed, Cmd
654 - Battery Test Condition Status
is set to
“Battery
Test Prohibited”
. It will be re-enabled once timer Cmd
655 - Battery Test Frequency
is reached.
Manual Battery Test:
The UPS must be in
Online
mode.
1.
Change the security setting to “ADMIN”.
2.
On the display, press the
Monitor
tab.
3.
On the display, press the
C&C
key.
4.
Use the Page (
<<
and
>>
) and Record (
<
and
>
) navigation keys to verify the following:
a. Cmd
652 - Battery Test Startup
must be set to
“Disable”
b. Cmd
653 - Enable Battery Test
set to
“Enable”
to allow the battery test to be performed.
c. Cmd
655 - Battery Test Frequency
should be set to
“0”
(Daily Test)
d. Cmd
654 - Battery Test Condition Status
should read
“Enable - Battery Test OK
to perform”
NOTE: If Cmd
654
is
“Disable”
, the user will have to power down and restart the unit to
perform the battery test.
e. Navigate to Cmd
609 - Requested State
and press the
“BattTest”
button on the display.
•
If the test passes, the display returns to the Monitor screen.
•
If the test fails, the display returns to the Monitor screen and displays BTSTFL in the warning
section at the bottom left of the display, and the “Warning” LED blinks until the fault is cleared.
11. Operating the UPS
The 1600XP/1600XPi should be installed by a certified electrician. Once installed, the 1600XP/1600XPi
is designed to be operated by any user. Anyone not familiar with this UPS should read the manual
before attempting to operate it.
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......