D11
1600XP/XPi Series Installation and Operation Manual – 60616-012
18kVA
–
UH3G2L180C61T / H3BG2L180C61T
(Runtimes are approximate)
UPS
ESTIMATED
RUNTIME WITH ONLY INTERNAL BATTERIES @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
18
0.7
240
75.00
0.10
1260
24
2
288
105
18
0.7
240
75.00
0.20
2520
24
2
288
57
18
0.7
240
75.00
0.30
3780
24
2
288
40
18
0.7
240
75.00
0.40
5040
24
2
288
27
18
0.7
240
75.00
0.50
6300
24
2
288
20
18
0.7
240
75.00
0.60
7560
24
2
288
16
18
0.7
240
75.00
0.70
8820
24
2
288
12
18
0.7
240
75.00
0.80
10080
24
2
288
10
18
0.7
240
75.00
0.90
11340
24
2
288
9
18
0.7
240
75.00
1.00
12600
24
2
288
7
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
18
0.7
240
75.00
0.10
1260
24
5
288
300
18
0.7
240
75.00
0.20
2520
24
5
288
135
18
0.7
240
75.00
0.30
3780
24
5
288
98
18
0.7
240
75.00
0.40
5040
24
5
288
72
18
0.7
240
75.00
0.50
6300
24
5
288
60
18
0.7
240
75.00
0.60
7560
24
5
288
50
18
0.7
240
75.00
0.70
8820
24
5
288
44
18
0.7
240
75.00
0.80
10080
24
5
288
37
18
0.7
240
75.00
0.90
11340
24
5
288
32
18
0.7
240
75.00
1.00
12600
24
5
288
27
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 2 MATCHING BATTERY CABINETS @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
18
0.7
240
75.00
0.10
1260
24
8
288
300
18
0.7
240
75.00
0.20
2520
24
8
288
180
18
0.7
240
75.00
0.30
3780
24
8
288
150
18
0.7
240
75.00
0.40
5040
24
8
288
112
18
0.7
240
75.00
0.50
6300
24
8
288
90
18
0.7
240
75.00
0.60
7560
24
8
288
78
18
0.7
240
75.00
0.70
8820
24
8
288
70
18
0.7
240
75.00
0.80
10080
24
8
288
60
18
0.7
240
75.00
0.90
11340
24
8
288
53
18
0.7
240
75.00
1.00
12600
24
8
288
48
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......