background image

 
 

Document 

No: 

373-1071 

Rev: 

Issue Date :

 

11/8/2021

 

Page: 

1  

Title: 

Instruct, Install,  Wireless Output Brd, DXI

 

O riginator :

 

Ri c h a rd   K e ig ht l ey

 

Confidential Property of 

 

Riverside, California

 

Approx W eight: 

0.08 

lbs 

O riginating Location:

 

Riverside

 

Page  count: 

Sheet count: 

Re lease/Change Authorization 
Number:  

5174342

 

 
 
 
 
 

Printing instructions: 

 

gray-scale 

 
 
 
 

See subsequent

 

pages for  

 original PDF

 

 
 
 
 
 
 
 

REVISION SHEET  

Re v. 

EC M No. 

De scription of C hange 

Drafter 

Date 

Approved 

By 

5174342 

Release  to rev A

 

Richard Keightley 

11/8/2021

 

Shankara 

Raghuraman

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for DXi

Page 1: ...iverside California Approx Weight 0 08 lbs OriginatingLocation Riverside Page count 8 Sheet count 4 Release Change Authorization Number 5174342 Printing instructions gray scale See subsequent pages for original PDF REVISION SHEET Rev ECM No Description ofChange Drafter Date Approved By A 5174342 Release to rev A Richard Keightley 11 8 2021 Shankara Raghuraman ...

Page 2: ... a wall stud If installing the controller on masonry or drywall use the appropriate type screw anchors and fasteners 2 Install the screw anchors at 83 4 22 23cm A on center Caution All cabinet openings required for installation and wiring are provided Drilling or cutting through the cabinet should be avoided Metal chips and filings entering the cabinet can damage internal components 3 Install the ...

Page 3: ...LINE AND NEUTRAL POLES ENSURE THE AC POWER SOURCE IS OFF PRIOR TO SERVICING FAILURE TO COMPLY MAY RESULT IN SERIOUS INJURY DUE TO ELECTRICAL SHOCK HAZARD 1 Ensure the power is disconnected at the source See Warning above 2 Remove the terminal block cover located below the transformer 3 Route the AC power and equipment ground wires through electrical conduit into the controller 4 Strip wire ends to...

Page 4: ... the controller The top of the ground rod should be buried approximately 12 30 5cm below grade 2 Route a 6 AWG 13 0mm2 solid copper wire connected to the earth ground device into the controller cabinet through the access hole provided below the copper ground lug Insert and secure the copper wire to the ground lug To provide the most efficient path to earth ground route the ground wire between the ...

Page 5: ... each wire 3 Connect the valve common wire s to terminal marked VC COM 4 Connect each valve power wire to the appropriate station number terminal See Figure 5 5 Pull lightly on each wire to confirm positive retention 6 Ensure all exposed wiring inside the controller is taped back and properly insulated 7 To release depress the small tab nearest the wire using a small blade screwdriver Output Switc...

Page 6: ...om of the WOB One terminal is marked FLOW1 the other FLOW2 see Figure 8 Caution To prevent damage to the controller and or sensor equipment turn off power to the controller prior to connecting sensor wires Installation Notes The ALARM terminal is not used The sensor connection terminals accept 16 28 AWG 1 5mm2 0 08mm2 solid core copper wire To enable positive wire retention insulation must be remo...

Page 7: ... switch Once a board is in Training Mode the next WOB communication it detects will cause the precode in the communication to be learned so that from that point forward the board will only listen to communications with that precode This allows multiple DXi controllers to run WOBs with the same board numbers within radio range since each WOB only listens to the precode of its master Once a board is...

Page 8: ... switch A 10 B 11 C 12 D 13 E 14 and F 15 To test communication Send ATaaaaabb Response aaaaa bb WOB ver 0 51 or current version To read k factor Send ATaaaaabbKc where c is the flow input number 1 or 2 Response aaaaa bb Kc K setting here To set k factor Send ATaaaaabbKc ddd ddd where ddd ddd is desired k factor padded with zeros Response aaaaa bb Kc Set To read offset Send ATaaaaabbOc Response aa...

Page 9: ...se contenu dans le présent appareil est conforme aux CNR d innovation Science et Dévellopement économique Canada applicables aux appareils radio exempts de licence L exploitation est autorisée aux deux condtions suivantes 1 l appareil ne doit pas produire de brouillage et 2 l appareil doit accepter tout brouillage radioélectrique subi même si le brouillage est suceptible d en compromettre le fonct...