8(16)
2 Assembly Instructions
2.1 General:
The product must be installed by a person who has the professional knowledge
required to perform the installation correctly. Unless the installation is performed
by a professional, the insurance companies may claim that the insurance does
not cover any damage that has occurred and that the offers made by the
insurance companies to the property owner are invalid.
If the ball valves are open for more than three days, they are exercised
automatically. This is done by partially closing the ball valves and then opening
them once. The water is never completely shut off. The water detectors
send signals every day which are registered by the control unit. If no signal
is perceived by the control unit for 72 hours, the control unit warns that
communication is down.
A total of 16 external units can be installed, mixed freely between remote devices
and water detectors.
A washing machine can be placed in the kitchen without a floor drain, if there
is a waterproof surface and a water detector connected to a water switch, by
wire or wireless, is placed so that any water leaking from the equipment can be
detected so that the leak can be automatically stopped. (According to Safe Water
Installation 2016: 1 Section 3.6.3) This of course also applies to other pressurised
equipment such as dishwashers, coffee machines, and refrigerators / freezers
with automatic water supply.
The products are marked with a label stating the article number and the date of
manufacture.
2.2 Installation:
Motorised Ball Valves: (art.no. 2130051 if DN15 is used)
The units are intended for tap water, 0-60°C and 0-10 bar.
Mount on cold and hot water. They can be mounted horizontally, vertically,
or upside down and independent of flow direction. The unit has an internal
R-thread. Connect them to pipes, for example with compression fittings. Use the
required sealant.
The units must not be mounted in a concealed place; they must be placed so that