12
d Connecting
“
RESET
”
and
“
LS IN
”
If you would like to connect to the "RESET" and "LS IN" terminal please use a non-contact
voltage switch. Example, LS torque wrench, relay, etc.
Do not feed the external power to input circuit to prevent damage.
EMI filter
EMI filter
Internal circuit
RESET
Vcc
LS-IN
Photocouple
r
Photocoupler
Non-voltage
contact switch
Non-voltage
contact switch
e Relay output from OUT1, OUT2, OUT3 and OUT4.
Relay
Relay
Internal circuit
OUT
1
OUT
4
Load
External power
Load
External power
・・・・
Set the load of the contact output within the rated load. Relay output rating: DC30V 1A, AC125V
0.5A. The above rated contact capacity is according to resistance load. Some kinds of loads have a
big difference between the steady-state current and the inrush current. Typical loads and inrush
currents are as follows:
Kind of Load
Inrush Current
Resistive Load
1 time as large as the steady-state current
Solenoid Load
10 to 20 times as large as the steady-state current
Motor Load
5 to 10 times as large as the steady-state current
Incahdescent Lamp
10 to 15 times as large as the steady-state current
Mecury Vapor Lamp
About 3 times as large as the steady-state current
Sodium Vapor Lamp
1 to 3 times as large as the steady-state current
Capacitor Load
20 to 40 times as large as the steady-state current
Trans Load
5 to 15 times as large as the steady-state current