TX7302 Addressable Flashing Beacon Base
Installation & Operation Manual
1.
Tone 14 – Volume dB(A)
Table 2 Sound pressure level of tone 14 at
different bus voltage with 3 meters away
Angle
(3m)
Horizontal Plane
Vertical Plane
Max 28V
Min 16V
Max 28V
Min 16V
15°
81.1
83.5
79.8
81.1
45°
77.7
80.5
78.1
80.2
75°
79.5
81.1
75.7
77.9
105°
81.1
82.6
77.4
80.3
135°
79.4
82.4
76.4
80.4
165°
80.4
84.1
78.8
79.2
2.
Tone 16 – Volume dB(A)
Table 3 Sound pressure level of tone 16 at
different bus voltage with 3 meters away
Angle
(3m)
Horizontal Plane
Vertical Plane
Max 28V
Min 16V
Max 28V
Min 16V
15°
79.8
80.8
79.0
80.0
45°
79.9
80.4
78.4
80.9
75°
80.5
80.1
77.9
79.1
105°
81.8
81.4
78.9
79.6
135°
78.3
79.4
77.9
77.8
165°
79.1
79.9
78.2
79.2
3.
Tone 17 – Volume dB(A)
Table 4 Sound pressure level of tone 17 at
different bus voltage with 3 meters away
Angle
(3m)
Horizontal Plane
Vertical Plane
Max 28V
Min 16V
Max 28V
Min 16V
15°
81.1
79.6
72.6
72.5
45°
74.5
78.6
73.2
70.6
75°
74.3
76.5
71.7
71.1
105°
74.7
80.7
76.2
76.1
135°
71.7
74.5
74.5
75.2
165°
75.1
75.2
73.7
71.1
Limitation of Addressable Flashing Beacon Base
The alarm warning device cannot last forever. In order to keep the alarm warning device working in
good condition, please maintain the equipment continuously according to recommendations from
manufacturers and relative nation codes and laws. Take specific maintenance measures on the
4050100452-Rev1.0-0917
TANDA UK
Specifications are subject to change without prior notice
11