172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
40
3.3 Parameter Select Mode [B]
Up to 16 screens registered on the Parameter select setting screen (Set data lock
mode) by the user can be displayed.
3.4 Operation Transfer Mode [C]
No.
Symbol
Name
Data range
Factory set
value
User set
value
15
R/S
RUN/STOP transfer
rUn
: RUN (Control start)
SToP
: STOP (Control stop)
STOP
16
1. ATU
Input 1_Autotuning
(AT)
1)
oFF
: PID control
on
: Start Autotuning
When the Autotuning (AT) is finished, the
control will automatically return to “
oFF
.”
oFF
17
2. ATU
Input 2_Autotuning
(AT)
2)
oFF
: PID control
on
: Start Autotuning
When the Autotuning (AT) is finished, the
control will automatically return to “
oFF
.”
oFF
18
1. STU
Input 1_Startup tuning
(ST)
1)
oFF
: ST unused
on1
: Execute once *
on2
: Execute always
* When the ST is finished, the control will
automatically return to “
oFF
.”
oFF
19
2. STU
Input 2_Startup tuning
(ST)
2)
oFF
: ST unused
on1
: Execute once *
on2
: Execute always
* When the ST is finished, the control will
automatically return to “
oFF
.”
oFF
20
1. A/M
Input 1_Auto/Manual
transfer
AUTo
: Auto mode
MAn
: Manual mode
MAN
21
2. A/M
Input 2_Auto/Manual
transfer
3)
AUTo
: Auto mode
MAn
: Manual mode
MAN
22
R/L
Remote/Local transfer
4)
When “Remote setting input” is selected at
Select function for Input 2
5)
LoC
: Local mode
rEM
: Remote mode
LoC
When
“Cascade control” is selected at Select
function for input 2
6)
SnGL
: Single control
CAS
: Cascade control
SnGL
When “Control with PV select” is selected at
Select function for input 2
7)
InP1
: Input 1
InP2
: Input 2
InP1
When “2-loop control/Differential
temperature control” is selected at Select
function for input 2
8)
2LooP
: 2-loop control
dIFF
: Differential temperature control
2LooP
23
L/E
Control area Local/
External transfer
9)
LoC
: Local mode
EXT
: External mode
LoC
1)
Not displayed when "Pressure control operation [MC-(V)COS(R)]" is selected in "Input 1_Control action".
2)
Displayed when "2-loop control/Differential temperature control" is selected in "Select function for Input 2" AND "Pressure control
operation [MC-(V)COS(R)]" is not selected in "Input 2_Control action".
3)
Displayed when one of "Remote setting input", "Cascade control", "Control with PV select", or "2-loop control/Differential
temperature control" is selected, AND in the case of "2-loop control", "PID control" or "Heating/Cooling PID control" is selected in
both Input 1_Control action and Input 2_Control action.
4)
Displayed when "Remote setting input" is selected in "Select function for Input 2."
5)
Displayed when "Cascade control" is selected in "Select function for Input 2."
6)
Displayed when "Control with PV select" is selected in "Select function for Input 2." When "Switching by level" is selected at
"Selection of PV select trigger," the parameter becomes display only.
7)
Displayed when "Control with PV select" is selected in "Select function for Input 2." When "Switching by level" is selected at
"Selection of PV select trigger," the parameter becomes display only.
8)
Displayed when "2-loop/differential temperature control" is selected in "Select function for Input 2" AND "PID control" or
"Heating/Cooling PID control" is selected both in Input 1 and Input 2.
9)
Displayed when "Memory area transfer (without area set signal)" is selected in DI function selection.
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...