310
8.18 Suppressing Overshoot
Overshoot can be suppressed at PID control at the time of startup (power on, control
stop to start), Set value (SV) change, and external disturbances.
Overshoot during the transition from Ramp to Soak can be prevented, when the
Setting change rate limiter is used.
Description of function
Overshoot suppressing function may include Control response parameter, Proactive
intensity, Determination point of external disturbance and Bottom suppression function.
Control response parameter
A response speed level at changing Set value (SV) at PID control can be selected
from three levels (Slow, Medium and Fast) in the Control response parameter.
Select “Fast” to quicken the response of the controlled object to the change in
segment level and Set value (SV).
When the response speed level is “Fast”,
overshoot will occur.
To avoid overshoot, select “Slow.”
Fast
Selected when rise time needs to be shortened (operation needs to started
fast). However in this case, slight overshooting may not be avoided.
Medium
Middle between “Fast” and “Slow.” Overshooting when set to “Medium”
becomes less than that when set to “Fast.”
Slow
Selected when no overshooting is allowed. Used when material may be
deteriorated if the temperature becomes higher that the set value.
Proactive intensity, Determination point of external disturbance
Overshoot can be suppressed at startup (power on, control stop to start), Set value
(SV) change, and external disturbances. Overshoot during the transition from Ramp
to Soak can be prevented. The intensity ranges from 0 to 4 (5 scales).
Startup (power on, control stop to start), Set value (SV) change
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...