172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
280
8.14 Executing Cascade Control
During the Cascade control, the measured value of the controlled object is monitored
by the Master, and depending on the deviation between the target value (set value)
and the actual value, the set value of the Slave is adjusted. The controlled object is
controlled by the Slave to bring the measured value of the controlled object to the
target value.
On the SC-F71, Input 1 can be assigned to the Master and Input 2 to the Slave
respectively to conduct Cascade control on a single instrument. The use of
Autotuning (AT) exclusively designed for the Cascade control allows the PID values
of both the Master and the Slave to be calculated.
Description of function
The Cascade control has two types; One is to switch between “Cascade control” and
“Master single control” and the other is to switch between “Cascade control” and
“Slave single control.”
The internal processing of the control is described below.
[Description of Cascade control]
Input 1_
Input 1_Setting
change rate limiter
Input 1_Set value
(SV)
Input 1 (PV1)
Input 1_PV ratio
Input 1_PV bias
Input 1_
PV digital filter
Setting limiter
Input 2 (PV2)
Input 2_PV ratio
Input 2_PV bias
Input 2_
PV digital filter
PID calculation
1
[Master]
Cascade_Digital filter
Output
Manipulated output 1 (MV1)
Output assignment
Cascade Scaling
PID calculation
2
[Slave]
Input 1_Output limiter
Input 1_Output
change rate limiter
1.
Use the Master side PID values of Cascade control
2.
Use the Slave side PID values of Cascade control
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...