172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
199
8. Control Function
This chapter describes control related functions, setting contents and setting
procedure based on the key words related to controls.
8.1 Running/Stopping Control (RUN/STOP Transfer)
Choose whether to start (RUN) or stop (STOP) control. The RUN/STOP transfer can
be made by Digital input (DI) or Communication (optional) other than the key
operation. The factory set value is STOP. As soon as the controller is powered on,
control is stopped.
State of this instrument when set to STOP mode
STOP display
Displays the STOP symbol “
SToP
” on the SV, PV or MV
displays.
(Factory set value: SV displays)
Control output
PID control
“Input 1_Manipulated output value at STOP [heat-side]” is
output.
(
Factory set value: -5.0%
)
“Input 2_Manipulated output value at STOP” *
is output.
(
Factory set value: -5.0%
)
* In the case of 2-loop control/Differential temperature control
Heating/Cooling
PID control
Heat-side:
“Input 1_Manipulated output value at STOP
[heat-
side]” is output.
(Factory set value: -5.0%)
Logic calculation output
According to the setting contents of Output action at STOP
(Factory set value: OFF)
Retransmission output
Instrument status output
Autotuning or Startup tuning
AT cancelled (PID constants are not updated.)
Refer to 9.4 Changing the Display Position of STOP during the Control Stop for
STOP display selection.
Refer to 6.9 Changing the Output Action While in Control Stop Mode for Action
selection at STOP mode.
State of this instrument when set to RUN mode
Operation when transferred to RUN from STOP is in accordance with the Hot/Cold
start selection setting.
Refer to 8.19 Changing the Action at Power ON (Hot/Cold Start) for Hot/Cold
start.
Refer to the SC-F71 Instruction Manual [Host communication] (172-65711M) for
RUN/STOP switching by communication (optional).
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...