background image

Note: Connection thread type is Rc(PT). 

 

Installation Manual 

PowerTrap

 GT5C   

Steam Trap Set   
for Motive Line

 

 

Safety Considerations 

  Read this section carefully before use and be sure to follow the instructions. 

  Installation, inspection, maintenance, repairs, disassembly, adjustment and valve opening/closing 

should be carried out only by trained maintenance personnel. 

  The precautions listed in this manual are designed to ensure safety and prevent equipment damage 

and personal injury.   

  The cautionary items are very important for safety: be sure to observe all of them as they relate to 

installation, use, maintenance, and repair. Furthermore, TLV accepts no responsibility for any 
accidents or damage occurring as a result of failure to observe these precautions.

 

 

Symbol 

 

CAUTION 

 

Indicates that there is a possibility of injury or equipment / product damage

 

 

CAUTION 

 

Install properly and DO NOT use this product outside the recommended operating 
pressure, temperature and other specification ranges. 

Improper use may result in such hazards as damage to the product or malfunctions that may 
lead to serious accidents. Local regulations may restrict the use of this product to below the 
conditions quoted. 

Take measures to prevent people from coming into direct contact with product outlets. 

Failure to do so may result in burns or other injury from the discharge of fluids. 

When disassembling or removing the product, wait until the internal pressure equals 
atmospheric pressure and the surface of the product has cooled to room temperature. 

Disassembling or removing the product when it is hot or under pressure may lead to discharge 
of fluids, causing burns, other injuries or damage.

 

NEVER attempt to modify the product in any way. (Replacement parts are not supplied 
individually. Replace as a set.) 

Failure to observe these precautions may result in damage to the product and burns or other 
injury due to malfunction or the discharge of fluids. 

Specifications 

Steam Trap 

TLV 10 mm (3/8 in)    LV21-C (X-element: C22 type) 

Maximum Allowable Pressure (PMA)

Maximum Allowable Temperature (TMA)

*

 

1.0 MPaG (150 psig) 

220 

C (428 

F) 

Maximum Operating Pressure (PMO) 
Maximum Operating Temperature (TMO) 

0.5 MPaG (75 psig) 

185 

C (365 

F) 

Applicable Fluids 

Saturated Steam 

(1 MPa 

 10.197 kg/cm

2

The same specifications apply to both cast iron and stainless steel types. 
* Maximum Allowable Pressure (PMA) and Maximum Allowable Temperature (TMA) are PRESSURE SHELL 

DESIGN CONDITIONS, 

NOT

 OPERATING CONDITIONS. 

 

 

 

General Description 

This product is a steam trap set designed to ease installation of the motive medium supply pipe for the 
GT5C. Stable operation of the GT5C can be obtained due to smooth condensate removal from the 
motive medium supply pipe by the LV21-C steam trap.   

Steam Trap

Strainer

Strainer

Steam Trap Set for 

Motive Line

Valve on 

Motive Medium 

Supply Pipe

Valve on 

Motive Medium 

Supply Pipe

 

Normal piping arrangement 

Piping arrangement with a steam trap set 

Installation & Operational Consideration 

 

CAUTION 

 

Before installing the product, blow out the piping to remove any piping scraps, dirt, oil 
and scale. 

Failure to do so may lead to early clogging due to an initial heavy load of foreign 

material in the piping.

 

Do not remove the product from its box or protective covering until just prior to 
installation. 

The protective covers keep damage causing foreign material out of the product.

 

  After the product is installed, it will look like the figure shown below. Installation, removal, or 

disassembly should be carried out by trained personnel. 

The product is available for cast iron or stainless steel types depending on the material used 
for the PowerTrap GT5C. The joint for lower part of the tube is not available for the cast iron 
type.

 

 

 

Installation procedure 

1.  Some parts for this product are not tightened completely at the time of shipment in order to avoid 

damage to the product during transportation. 

Spread a work cloth or a sheet on the floor 

before installation in order to prevent dropping and losing parts. 

Then remove the product 

from the package and loosen the union joint for the tube to disconnect the tube.   

Loosen the union

Be careful not to 

drop parts

Joint for stainless steel
tube is not tightened 
completely at time of
shipping. Please be
careful not to drop parts. 

Disconnect the tube

 

Copper tube

 

Stainless Steel tube

 

Condensate
inflow

Steam Trap Set for Motive Line

Motive Medium 

Inlet

Joint for 

stainless tube. 

Not for cast iron type.

(Remove the plug

before installation)

 

Cast Iron Type 

Stainless Steel Type 