172-65454MA-03 (JH7RL-X) 20 Oct 2020
15
Options
The options shown below are available for this product on
request. Please compare with the product you received.
Options for Area A
(standard: with drain plug)
Without Drain Plug
Options for Area B
(standard: no equipment)
Use gloves when operating the needle valve and keep all body parts well
clear of the product. Failure to do so could result in burns, other injury or
damage from the blowing of small amounts of steam and condensate.
CAUTION
Operating Instructions for Needle Valve
1. When shipped from the factory, the needle valve is in the closed position.
2. To operate the needle valve, insert a flat-head screwdriver into the slot on the top
of the needle valve and:
- Open Valve: slowly turn counterclockwise. (Do not continue turning the needle
valve past the point at which the snap ring contacts the bottom of the gland case.)
See the table below to determine the amount of steam discharge
- Close Valve: slowly turn clockwise. (Do not continue turning the needle valve
past the point at which it stops.)
3. If steam should leak from the gland retainer nut or gland case, it can be stopped
by further tightening the gland retainer nut. (Do not over tighten, otherwise the
needle valve may seize and become unworkable.)
Needle Valve Unit (Model: JH7RL-NV)
Gland Case
Torque: 30 N
∙m (22 lbf∙ft)
19 mm ( ¾” ) across flats
Gland Packing
Gasket
Gland Retainer Nut
Torque: 30 N
∙m (22 lbf∙ft)
22 mm (
7
8
” )
across flats
Needle Valve
Snap Ring